3 Function diagrams
3.21 Terminal Board 30 (TB30)
SINAMICS G130/G150
1236 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-182 9104 – Analog inputs (AI 0 ... AI 1)
x
- 9104 -
Function diagram
87654321
fp_9104_51_eng.vsd
DO: TB30
SINAMICS
21.06.05 V04.07.00
Terminal Board 30 (TB30) - Analog inputs (AI 0 ... AI 1)
AI 1
Scaling
r4055[1]
p4069[1]
(1)
Enable
Hardware
smoothing 100 μs
p4066 [1]
(0)
p4067[1]
y = x if
|y - x| > p4068
otherwise y = y(old)
y
x
A
D
Offset
-20.000...20.000 V
p4063[1] (0.000)
-11.000...11.000 V
p4057[1] (0.000)
-11.000...11.000 V
p4059[1] (10.000)
[V]
r4052[1]
p4097.1
-1000.00...1000.00 %
p4060[1] (100.00)
-1000.00...1000.00 %
p4058[1] (0.00)
X482.3
X482.4
AI 0
Scaling
r4055[0]
p4069[0]
(1)
Enable
Hardware
smoothing 100 μs
p4066 [0]
(0)
p4067[0]
y = x if |y - x| > p4068
otherwise y = y(old)
y
x
A
D
Offset
-20.000...20.000 V
p4063[0] (0.000)
-11.000...11.000 V
p4057[0] (0.000)
-11.000...11.000 V
p4059[0] (10.000)
[V]
r4052[0]
p4097.0
Simulation mode
-11.000...11.000 V
p4098[0] (0.000)
-1000.00...1000.00 %
p4060[0] (100.00)
-1000.00...1000.00 %
p4058[0] (0.00)
X482.1
X482.2
+
-
0 %
Smoothing
0.0...1 000.0 ms
p4053[0] (0.0)
Window to suppress noise
0.00...20.00 %
p4068[0] (0.00)
Smoothing
0.0...1 000.0 ms
p4053[1] (0.0)
Window to suppress noise
0.00...20.00 %
p4068[1] (0.00)
[%]
[%]
0 %
1
0
1
0
<1> When interconnected
further, the output
signals are referred to
the reference
quantities
p2000 ... r2004
(100 % p200x).
<1>
+
+
+
+
-11...+11 V
-11...+11 V
xy
xy
Reference quantities
p2000...r2004
y
x
2
x
1
Reference quantities
p200x
y
x
2
x
1
<2>
<2>
<3>
p4099[1] (4000.00 μs)
x
1
y
2
x
2
y
1
y
x
[%]
[V]
x
1
y
2
x
2
y
1
y
x
[%]
[V]
<1>
Simulation mode
-11.000...11.000 V
p4098[1] (0.000)
-1
0
1
-1
0
1
0
1
0
1
<3> Caution: The voltage
between an input and
the grounding point
must not exceed 35V.
The voltage between
the inputs must not
exceed 35V.
1
0
1
0
<3>
x
% 100
xx
21
<2> Differential inputs!
For input signals
referred to ground,
terminal 2
and/or terminal 4
must be connected to
the reference
potential M.
+
-