EasyManua.ls Logo

Siemens SINAMICS G150 - Page 1242

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Function diagrams
3.22 Communication Board CAN10 (CBC10)
SINAMICS G130/G150
1242 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-187 9210 – Send telegram, Predefined Connection Set (p8744 = 1)
- 9210 -
Function diagram
87654321
fp_9210_51_eng.vsd
DO: A_INFM2C, SERVO, VECTOR, VECTOR3P, VECTORGL, VECTORMV, VECTORSL
SINAMICS
05.07.13 V04.07.00
Communication Board CAN10 (CBC10) - Send telegram, Predef. Connection Set (p8744 = 1)
DWORD
63
p8861[1]
DWORD
(0)
p8861[2]
DWORD
(0)
p8861[3]
DWORD
492.0
p8861[4]
DWORD
(0)
p8861[0]
CANopen send telegram
X451
CAN bus
X452
CAN bus
DWORD
(0)
p8861[5]
DWORD
(0)
p8861[14]
DWORD
(0)
p8861[7]
DWORD
(0)
p8861[8]
DWORD
(0)
p8861[9]
DWORD
(0)
p8861[10]
DWORD
(0)
p8861[6]
DWORD
(0)
p8861[11]
DWORD
(0)
p8861[12]
DWORD
(0)
p8861[13]
(0)
p8851[1]
(0)
p8851[2]
79
p8851[3]
(0)
p8851[4]
8784
p8851[0]
(0)
p8851[5]
(0)
p8851[14]
(0)
p8851[7]
(0)
p8851[8]
(0)
p8851[9]
(0)
p8851[10]
(0)
p8851[6]
(0)
p8851[11]
(0)
p8851[12]
(0)
p8851[13]
(0)
p8851[15]
PZD send word 1
PZD send word 2
PZD send word 3
PZD send word 4
PZD send word 5
PZD send word 6
PZD send word 7
PZD send word 8
PZD send word 9
PZD send word 10
PZD send word 11
PZD send word 12
PZD send word 13
PZD send word 14
PZD send word 15
IF2 Diag PZD send
r8853[0...15]
...
PZD send word 16
<1> Telegram: up to 4 words or 64 bits.
The sum of the various objects must not exceed 16 words.
Object 4
COB-ID
Object 1
Evaluation of
the COB-ID
and data
transfer type.
COB-ID for TPDO 1
p8720[0]
PDO mapping for TPDO 1
p8730[0...3]
<1>
Send buffer
Automatic assignment of
send buffer to the TPDOs
60410010
60410010
606C0020
p8723[0]
60410010
60630020
p8733[0...3]
p8722[0]
60410010
60740010
p8732[0...3]
p8721[0] p8731[0...3]
The assignment
is made from
the send buffer
1 and from
TPDO 1.
Objects that occur
a multiple number
of times are
updated from the
same send buffer.
TPDO 1
TPDO 2
TPDO 3
TPDO 4
TPDO: Transmit Process Data Object
COB-ID: CAN Communication Object Identifier
CAN bus sampling time
CANopen send words 1...16

Table of Contents

Other manuals for Siemens SINAMICS G150

Related product manuals