3 Function diagrams
3.24 Terminal Module 150 (TM150)
SINAMICS G130/G150
1258 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-201 9626 – Temperature evaluation 1x2, 3, 4 wire (channels 0 ... 5)
- 9626 -
Function diagram
87654321
fp_9626_51_eng.vsd
SINAMICS
04.12.12 V04.07.00
Terminal Module 150 (TM150) - Temperature evaluation 1x2, 3, 4 wire (channels 0  5)
DO: TM150
X53x.1
X53x.2
X53x.3
X53x.4
x = 1, 2,
3, 4, 5, 6
Sensor R
r4101[0...5] 1650 (PTC)
100  (Bimetal)
KTY84
PTC/
Bimetal
NC
contact
Sensor type
p4100[0...5]
<2>
26000.00 μs
A
D
Calculate
resistance
0
1
R
T
250 °C
-99 °C
KTY84
PTC
-50 °C
250 °C
1 0
Bimetal
-300 °C
6
5
4
2
1
0
PT100
PT1000
PT100
R
T
250 °C
-99 °C
PT1000
R
T
250 °C
-99 °C
p4119[0...5]
p4108[0...5] = 0, 2, 3
50/60 Hz
Cable R meas
p4109[0...5]
Cable R value
p4110[0...5]
10
Determine cable resistance
(with short-circuited sensor)
+
Save cable
resistance
<4>
r4104.0
"Channel y alarm is present"
A35920  A35925
"Error temperature sensor channel y"
(y = 0  5)
r4105[0...5]
Temp act value
Alarm is present
-300 °C
1
Alarm threshold
-99...251 [°C]
p4102[0, 2, 4, 6, 8, 10] (251)
Fault threshold
-99...251 [°C]
p4102[1, 3, 5, 7, 9, 11] (251)
<1>
1
0
only for
KTY84, PT100,
PT1000
Group formation
p4118[0...5] (5)
r4104.2
r4104.4
r4104.6
r4104.8
r4104.10
r4104.1
"Channel y fault is present"
r4104.3
r4104.5
r4104.7
r4104.9
r4104.11
0
1
0
1
[9625.6]
Measuring
method
0: 1x2 wire
1: 2x2 wire
2: 3 wire
3: 4 wire
[9625]
Temp filt T
r4120
<1>
<4>
<1> For p4102[0...23] = 251 °C the evaluation of the appropriate threshold is deactivated.
<2> p4100[0...11]
= 0: Evaluation disabled
= 1: PTC thermistor (with monitoring for short-circuit)
= 2: KTY84 (with monitoring for wire break and short-circuit)
= 4: Bimetal NC contact (no monitoring)
= 5: PT100 (with monitoring for wire break and short-circuit)
= 6: PT1000 (with monitoring for wire break and short-circuit)
<3> For p4103 = 0 s and sensor type "KTY84", "PT100", "PT1000" (p4100[0...11] = 2, 5, 6) the following applies:
- The relevant fault can only be triggered via the fault threshold (the timer output is always logical 0).
For p4103 = 0 s and sensor type "PTC thermistor", "Bimetal NC contact" (p4100[0...11] = 1, 4) the following applies:
- The corresponding alarm and fault are output simultaneously (delay time = 0 s).
<4> Only for 1x2/2x2 wire evaluation (p4108[0...5] = 0, 1).
F35401 (Channel 5)
F35400 (Channel 4)
F35210 (Channel 3)
F35209 (Channel 2)
F35208 (Channel 1)
F35207 (Channel 0)
A35411 (Channel 5)
A35410 (Channel 4)
A35214 (Channel 3)
A35213 (Channel 2)
A35212 (Channel 1)
A35211 (Channel 0)
Temperature actual value
T0
0.0...600.0 [s]
p4103[0...5] (0.0)
<3>
p4121 (0)
Filt f_line