3 Function diagrams
3.25 Voltage Sensing Module (VSM)
SINAMICS G130/G150
1262 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-204 9886 – Temperature evaluation
- 9886 -
Function diagram
87654321
fp_9886_54_eng.vsd
S120/S150/G130/G150
07.01.14 V04.07.00
Voltage Sensing Module (VSM) - Temperature evaluation
DO: A_INF, S_INF, VECTOR
X520.5
X520.6
Hardware
smoothing 1 s
r3664.1
r3664.0
Software smoothing
0.5 s
2 mA
-50 °C
0
1
Sensor type
p3665 (0)
PTC resistor
threshold 1650 Ohm
T
R
1
0
250 °C
KTY
PTC
188,6 °C
-140 °C
A
D
Resistance
calculation
+
-
+ temp
- temp
<1>
<1> p3665 = 0: No sensor
= 1: PTC
= 2: KTY
<1>
r3666
Temperature KTY
4000.00 μs
0
1
0
1
<3>
<4>
<4>
Sensor resistance
[9887.1]
<2> A fault or alarm in the temperature evaluation of the VSM is communicated to the downstream evaluation using special temperature values.
<3> As a result of the wire breakage monitoring the maximum temperature that can be measured is limited to approx. 175 °C.
<4> When using a PTC, a value exceeding 250 °C deactivates the warning resp. fault.
When using a KTY, a value exceeding 188.6 °C deactivates the warning resp. fault.
<5> Can only be used with chassis infeeds.
<6> The VECTOR drive object is assigned a dynamic index (p0150).
<5>
<6>
<6>
<6>
<6>
<6>
0
1
2
No sensor
Temperature sensor
KTY/PTC
Alarm A35920
temperature sensor evaluation
<2>
Alarm is not present
Alarm is present
-300 °C
Sensor type
p3665 (0)
Overtemperature alarm threshold
0...301 [°C]
p3667[0] (150)
A34211
"Temperature alarm threshold exceeded"
F34207
"Temperature fault threshold exceeded"
Overtemperature fault threshold
0...301 [°C]
p3668[1] (180)
Overtemperature hysteresis
p3669