3 Function diagrams
3.26 Basic Operator Panel 20 (BOP20)
SINAMICS G130/G150
1264 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-205 9912 – Control word interconnection
- 9912 -
Function diagram
87654321
fp_9912_54_eng.vsd
DO: CU_G, CU_S
S120/S150/G130/G150
03.07.13 V04.07.00
Basic Operator Panel 20 (BOP20) - Control word interconnection
STW BOP.0
STW BOP.1
STW BOP.2
STW BOP.3
STW BOP.4
STW BOP.5
STW BOP.6
STW BOP.8
STW BOP.9
STW BOP.11
STW BOP.12
STW BOP.13
STW BOP.14
STW BOP.15
STW BOP.7
STW BOP.10
p0848[0] = r0019.2
-
-
-
-
p2102[0] = r0019.7
-
-
-
-
-
p1035[0] = r0019.13
p1036[0] = r0019.14
-
p0840[0] = r0019.0
p0844[0] = r0019.1
1 = On
0 = OFF (OFF1)
1 = No coast down
0 = Coast down (OFF2)
1 = No fast stop
0 = Fast stop (OFF3)
= Acknowledge fault
Reserved
Reserved
Reserved
1 = Motorized potentiometer, raise
Reserved
1 = Motorized potentiometer, lower
Interconnection STW BOP (r0019)
Signal
Interconnection
parameters
Meaning
PROFIdrive sampling time
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
<1>
<1> The BICO interconnection represents an example that can be be changed by the user.