4 Faults and alarms
4.1 Overview of faults and alarms
SINAMICS G130/G150
1270 List Manual (LH2), 04/2014, A5E03263479A
Fault buffer - saved when switching off
The contents of the fault buffer are saved to the non-volatile memory when the Control Unit is
switched off, i.e. the fault buffer history is still available when the unit is switched on again.
The fault buffer of a drive object comprises the following parameters:
r0945[0...63], r0947[0...63], r0948[0...63], r0949[0...63]
r2109[0...63], r2130[0...63], r2133[0...63], r2136[0...63]
The fault buffer contents can be deleted manually as follows:
Delete fault buffer for all drive objects:
p2147 = 1 --> p2147 = 0 is automatically set after execution.
Delete fault buffer for a specific drive object:
p0952 = 0 --> The parameter belongs to the specified drive object.
The fault buffer contents are automatically deleted when the following occurs:
Restore factory setting (p0009 = 30 and p0976 = 1).
Download with modified structure (e.g. number of drive objects changed).
Power-up after other parameter values have been loaded (e.g. p0976 = 10).
Upgrade firmware to later version.