4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1282 List Manual (LH2), 04/2014, A5E03263479A
A01009 (N) CU: Control module overtemperature
Message value: -
Message class: Overtemperature of the electronic components (6)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: The temperature (r0037[0]) of the control module (Control Unit) has exceeded the specified limit value.
Remedy: - check the air intake for the Control Unit.
- check the Control Unit fan.
Note:
The alarm automatically disappears after the limit value has been undershot.
Reaction upon N: NONE
Acknowl. upon N: NONE
F01010 Drive type unknown
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: An unknown drive type was found.
Fault value (r0949, interpret decimal):
Drive object number (refer to p0101, p0107).
Remedy: - replace Power Module.
- carry out a POWER ON (power off/on) for all components.
- upgrade firmware to later version.
- contact the Hotline.
F01011 (N) Download interrupted
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The project download was interrupted.
Fault value (r0949, interpret decimal):
1: The user prematurely interrupted the project download.
2: The communication cable was interrupted (e.g. cable breakage, cable withdrawn).
3: The project download was prematurely ended by the commissioning software (e.g. STARTER, SCOUT).
100: Different versions between the firmware version and project files which were loaded by loading into the file
system "Download from memory card".
Note:
The response to an interrupted download is the state "first commissioning".
Remedy: - check the communication cable.
- download the project again.
- boot from previously saved files (power-down/power-up or p0976).
- when loading into the file system (download from memory card), use the matching version.
Reaction upon N: NONE
Acknowl. upon N: NONE