4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1498 List Manual (LH2), 04/2014, A5E03263479A
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
A07921 Drive: Torque/speed too high
Message value: -
Message class: Application / technological function faulted (17)
Drive object: VECTOR_G
Reaction: NONE
Acknowledge: NONE
Cause: The torque deviates from the torque/speed envelope characteristic (too high).
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
A07922 Drive: Torque/speed out of tolerance
Message value: -
Message class: Application / technological function faulted (17)
Drive object: VECTOR_G
Reaction: NONE
Acknowledge: NONE
Cause: The torque deviates from the torque/speed envelope characteristic.
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
F07923 Drive: Torque/speed too low
Message value: -
Message class: Application / technological function faulted (17)
Drive object: VECTOR_G
Reaction: OFF1 (NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: The torque deviates from the torque/speed envelope characteristic (too low).
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
F07924 Drive: Torque/speed too high
Message value: -
Message class: Application / technological function faulted (17)
Drive object: VECTOR_G
Reaction: OFF1 (NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: The torque deviates from the torque/speed envelope characteristic (too high).
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.
F07925 Drive: Torque/speed out of tolerance
Message value: -
Message class: Application / technological function faulted (17)
Drive object: VECTOR_G
Reaction: OFF1 (NONE, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: The torque deviates from the torque/speed envelope characteristic.
Remedy: - check the connection between the motor and load.
- adapt the parameterization corresponding to the load.