4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1806 List Manual (LH2), 04/2014, A5E03263479A
13: F CPU with more PROFIsafe subslots than activated with p9601.3.
14: F CPU with fewer PROFIsafe subslots than activated with p9601.3.
15: PROFIsafe telegram of the F-CPU does not match the setting in p60022.
See also: p8829 (CBE2x remote controller number), p9601 (SI enable functions integrated in the drive (Control Unit))
Remedy: CBE20:
Check the configuration of the PROFINET controllers as well as the p8829 and p9601.3 setting.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50002 (F) COMM BOARD: Alarm 2
Message value: %1
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: CBE20 SINAMICS Link:
A specific telegram word (send) is being used twice.
Alarm value (r2124, interpret decimal):
Telegram word used twice
See also: p8871 (SINAMICS Link send telegram word PZD)
Remedy: CBE20 SINAMICS Link:
Correct the parameter assignment.
See also: p8871 (SINAMICS Link send telegram word PZD)
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50003 (F) COMM BOARD: Alarm 3
Message value: Info. 1: %1, info. 2: %2
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: CBE20 SINAMICS Link:
A specific telegram word (receive) is being used twice.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = Address of sender
Info. 2 (decimal) = Receive telegram word
See also: p8870 (SINAMICS Link receive telegram word PZD), p8872 (SINAMICS Link address receive PZD)
Remedy: CBE20 SINAMICS Link:
Correct the parameter assignment.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY