4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1808 List Manual (LH2), 04/2014, A5E03263479A
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50010 (F) PN/COMM BOARD: Station name invalid
Message value: %1
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: CBE20:
PROFINET Name of Station is invalid.
Remedy: CBE20:
Correct the name of the station (p8940) and activate (p8945 = 2).
See also: p8940 (CBE2x Name of Station)
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50020 (F) PNCOMM BOARD: Second controller missing
Message value: -
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Reaction: NONE
Acknowledge: NONE
Cause: CBE20:
The PROFINET function "Shared Device" has been activated (p8829 = 2). However, only the connection to a
PROFINET controller is present.
See also: p8829 (CBE2x remote controller number)
Remedy: CBE20:
Check the configuration of the PROFINET controllers as well as the p8829 setting.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY