Parameter Value
Reference potential for all digital inputs and
outputs
Minus pole of the supply voltage, signal name
ZP
Setting of the IO device identifier With 2 rotary switches at the front side of the
module
Diagnose
See Diagnosis and Displays
Ä
Chapter
1.7.6.2.8 “Diagnosis and State LEDs”
on page 1030
Operation and error displays 32 LEDs (totally)
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load
reduced to 50 % at 40 °C per group)
Extended ambient temperature (XC version) >60 °C on request
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
Parameter Value
Bus connection 2 x RJ45
Switch Integrated
Technology Hilscher netX100
Transfer rate 10/100 Mbit/s (full-duplex)
Transfer method According to Ethernet II, IEE802.3
Ethernet 100 base-TX, internal switch, 2x RJ45 socket
Expandability Max. 10 S500 I/O modules
Adjusting elements 2 rotary switches for generation of an explicit
name
Supported protocols RTC - real time cyclic protocol, class 1 *)
RTA - real time acyclic protocol
DCP - discovery and configuration protocol
CL-RPC - connectionless remote procedure
Call
LLDP - link layer discovery protocol
MRP - MRP Client
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/17 3ADR010121, 13, en_US 1041