Terminal Signal Description
2.2 DI10 Signal of the digital input DI10
2.3 DI11 Signal of the digital input DI11
2.4 DI12 Signal of the digital input DI12
2.5 DI13 Signal of the digital input DI13
2.6 DI14 Signal of the digital input DI14
2.7 DI15 Signal of the digital input DI15
2.8 UP Process voltage UP (24 VDC)
2.9 ZP Process voltage ZP (0 VDC)
3.0 DO8 Signal of the digital output DO8
3.1 DO9 Signal of the digital output DO9
3.2 DO10 Signal of the digital output DO10
3.3 DO11 Signal of the digital output DO11
3.4 DO12 Signal of the digital output DO12
3.5 DO13 Signal of the digital output DO13
3.6 DO14 Signal of the digital output DO14
3.7 DO15 Signal of the digital output DO15
3.8 UP3 Process voltage UP3 (24 VDC)
3.9 ZP Process voltage ZP (0 VDC)
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply and process voltage) are
switched off before you begin with operations at the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
The following figure shows the electrical connection of the Ethernet bus module CI502-PNIO.
Device Specifications
Communication Interface Modules (S500) > PROFINET
2019/04/173ADR010121, 13, en_US1050

Table of Contents

Related product manuals