WARNING!
For screw terminals only: Danger of death by electric shock!
The IP 20 protection degree is only provided if all terminal screws are tightened.
Tighten all screws of unused load terminals of relay outputs if voltages > 24 V
are connected to the relay group.
Table 201: Screw-type Terminals (TA563/TA564)
Parameter Value
Type Front terminal or side terminal (depending on
model)
Conductor cross section
Solid
0.5 mm
2
to 2.5 mm
2
Flexible
0.5 mm
2
to 2.5 mm
2
Stripped conductor end
TA563 8 mm
TA564 10 mm
Width of the screwdriver 3.5 mm
Fastening torque 0.4 Nm - 0.5 Nm
Degree of protection IP 20 (if all terminal screws are tightened)
Conductor cross section flexible, with ferrule
with/without plastic sleeve
Min. 0.25 mm
2
Max. 1.5 mm
2
Table 202: Spring Terminals (TA565)
Parameter Value
Type Front terminal
Conductor cross section
Solid
0.5 mm
2
to 2.5 mm
2
Flexible
0.5 mm
2
to 2.5 mm
2
Stripped conductor end 10 mm
Degree of protection IP 20
Conductor cross section flexible, with ferrule
with/without plastic sleeve
Min. 0.25 mm
2
Max. 1.5 mm
2
Part No. Description Product Life Cycle Phase *)
1TNE 968 901 R3101 Terminal Block TA563-9, 9-
pole, screw front, cable side, 6
pieces per unit
Active
1TNE 968 901 R3102 Terminal Block TA563-11, 11-
pole, screw front, cable side, 6
pieces per unit
Active
Technical Data
Ordering Data
Device Specifications
Accessories > S500-eCo
2019/04/17 3ADR010121, 13, en_US 1165