5. Insert replacement battery.
ð
ATTENTION!
A standard batterie CR2032 can be used for TA561-RTC and TA562-
RS-RTC.
Nominal voltage: 3 VDC.
Required capacity: 230 mAh.
Required temperature range for discharge: 0 °C...+70 °C.
After replacement of the battery, the real-time clock (RTC) date and
time must be set again by the user.
Don’t use a battery older than 3 years for replacement (e.g. battery
kept too long in stock).
Batteries must be stored in a dry place.