EasyManua.ls Logo

ABB AC500 PLC - Page 174

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Terminal Signal Description
19 UP Process voltage UP +24 VDC
20 ZP Process voltage ZP 0 VDC
The arrow located next to the Interfast connector marks terminal 1.
The internal power supply voltage for the module's circuitry is carried out via the I/O bus (pro-
vided by a bus module or a CPU). Thus, the current consumption from 24 VDC power supply at
the terminals L+/UP and M/ZP of the CPU/bus module increases by 10 mA per DC561.
The external power supply connection is carried out via the UP (+24 VDC) and ZP (0 VDC) ter-
minals.
WARNING!
Removal/Insertion under power
The devices are not designed for removal or insertion under power. Because of
unforeseeable consequences, it is not allowed to plug or unplug devices with
the power being ON.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
connect or disconnect any signal or terminal block
remove, mount or replace a module.
Disconnecting any powered devices while energized in a hazardous location
could result in an electric arc, which could create a flammable ignition resulting
in fire or explosion.
Make sure that power is removed and that the area has been thoroughly
checked to ensure that flammable materials are not present prior to proceeding.
The devices must not be opened when in operation. The same applies to the
network interfaces.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply and process voltage) are
switched off before you begin with operations at the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
Process supply voltage must be connected to UP/ZP of the module. The inputs
and UP/ZP must use the same power supply.
If DC561 with index A0 is used, the process supply voltage must stem from the
same source as the power supply voltage of the CPU. The index consists of 1
letter, followed by 1 digit, and can be found on the type plate of the module next
to the type designator "DC561".
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US174

Table of Contents

Related product manuals