Parameter Value
Indication of the output signals 1 yellow LED per channel; the LED is on when the
output signal is high (signal 1) and the module is
powered through the I/O bus
Monitoring point of output indicator Controlled together with relay
Way of operation Non-latching type
Relay output voltage
Rated value 24 VDC or 120/240 VAC
Output delay
Switching 0 to 1 (max.) Typ. 10 ms
Switching 1 to 0 (max.) Typ. 10 ms
Output data length 1 byte
Output current
Rated current per channel
(max.)
2.0 A (24 VDC / 24 VAC / 48 VAC / 120 VAC /
240 VAC, only resistive loads)
2.0 A (24 VAC / 48 VAC / 120 VAC, only pilot duty)
1.5 A (240 VAC, only pilot duty)
Rated current per group (max.) 8 A
Lamp load (max.) 200 W (230 VAC), 30 W (24 VDC)
Spark suppression with inductive AC
loads
Must be performed externally according to driven
load specification
Switching Frequencies
With resistive loads Max. 1 Hz
With inductive loads On Request
With lamp loads Max. 1 Hz
Output type Non-protected
Protection type External fuse on each channel
Rated protection fuse (for each
channel)
5 A fast
Short-circuit-proof / Overload-proof No, should be provided by an external fuse or circuit
breaker
Overload message No
Output current limitation No
Connection of 2 outputs in parallel Not possible
Life time of relay contacts (cycles) 100.000 at rated load
Max. cable length
Shielded 500 m
Unshielded 150 m
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/173ADR010121, 13, en_US296