No. Name Value Internal value Internal
value, type
Default
1 Channel con-
figuration
see below
Ä
 Table 64 “C
hannel Con-
figuration 
3
)”
on page 513
see below
Ä
 Table 64 “C
hannel Con-
figuration 
3
)”
on page 513
Byte see below
Ä
 Table 64 “C
hannel Con-
figuration 
3
)”
on page 513
2 Channel mon-
itoring
see below
Ä
 Table 65 “C
hannel Moni-
toring 
4
)”
on page 513
see below
Ä
 Table 65 “C
hannel Moni-
toring 
4
)”
on page 513
*8)
Byte see below
Ä
 Table 65 “C
hannel Moni-
toring 
4
)”
on page 513
3 Substitute
value
Ä
 Table 66 “S
ubstitute
Value”
on page 514
0...65535 0...
0xffff
Word 0
No. Name Internal value, type
1 Channel configuration
see table 
3
)
Byte
2 Channel monitoring
see table 
4
)
Byte
Table 64: Channel Configuration 
3
)
Internal value Operating modes of the analog outputs,
individually configurable
0 Unused (default)
128 Analog output -10 V...+10 V
129 Analog output 0 mA...20 mA (not with the
channels 4...7 and 12...15)
130 Analog output 4 mA...20 mA (not with the
channels 4...7 and 12...15)
Table 65: Channel Monitoring 
4
)
Internal value Monitoring
0 Plausibility, open-circuit (broken wire) and
short circuit (default)
1 Open-circuit (broken wire) and short circuit
2 Plausibility
3 No monitoring
Output Chan-
nels 0 and 8 (2
channels,
AO523)
Output Chan-
nels 1...7 and
9...15 (14 chan-
nels, AO523)
 
I/O Modules > Analog I/O Modules