EasyManua.ls Logo

ABB AC500 PLC - Page 692

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Inrush current from L+ (at
power up, FM502-CMS and
PM592-ETH, no communica-
tion module)
1.2 A
2
s
Galvanic isolation Yes, PM592-ETH and FM502-CMS to other I/O bus modules
Max. power dissipation within
the FM502-CMS
6.5 W (outputs unloaded)
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
For maritime applications a metal cabinet is required
Table 101: Technical Data of the Device
Parameter Value
Weight FM502-CMS 215 g
Weight FM502-CMS-XC 220 g
Mounting position Horizontal
Vertical with derating: max. temperature 40 °C
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switch-gear cabinet.
Deratings for operation of FM502-CMS-XC
between +60 °C and +70 °C
No use of 24 V encoder mode.
Analog inputs: maximum number of config-
ured input channels limited to 75 % per group
AI0...AI7 and AI8...AI15.
Required Terminal Base
TF501 or TF521
Ä
Chapter 1.1.2 “TF501-
CMS and TF521-CMS - Function Module Ter-
minal Bases ” on page 13
Table 102: Technical Data of the 5 V Encoder Supply
Parameter Value
Number of supplies 1
Connections Terminal 1.7
Rated value 5 VDC (+/- 5%)
Resistance to feedback against reverse
polarity
No
Device Specifications
Function Modules > S500
2019/04/173ADR010121, 13, en_US692

Table of Contents