EasyManua.ls Logo

ABB AC500 PLC - Page 699

ABB AC500 PLC
1315 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Ambient temperature
System data AC500
Ä
Chapter 2.6.1 “System
Data AC500” on page 1248
System data AC500 XC
Ä
Chapter 2.7.1
“System Data AC500-XC” on page 1309
Current consumption UP: 0.2 A UP3: 0.06 A + 0.5 A max. per output
Weight (without terminal unit) Ca. 125 g
Process supply voltages UP/UP3
Rated value 24 VDC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Galvanic isolation CANopen interface against the rest of the
module
Inrush current from UP (at power up) On request
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Reference potential for all digital inputs and
outputs
Minus pole of the supply voltage, signal name
ZP
Setting of the CANopen Node ID identifier With 2 rotary switches at the front side of the
module
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be hin-
dered by cable ducts or other parts in the
switch-gear cabinet.
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to
35 V
Required terminal unit
TU509, TU510, TU517 or TU518
Ä
Chapter
1.4.2 “TU509 and TU510 for Communication
Interface Modules” on page 149
Ä
Chapter
1.4.4 “TU517 and TU518 for Communication
Interface Modules” on page 158
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 VDC.
The difference of those devices can be found in their input and output characteristics.
Device Specifications
Communication Interface Modules (S500) > CANopen
2019/04/17 3ADR010121, 13, en_US 699