Chapter 18 DLPs A100 to A199
DLP-A173 Change External Alarms Using the AIC Card
DLP-A173 Change External Alarms Using the AIC Card
Step 1 Confirm that external-device relays are wired to the ENVIR ALARMS IN backplane pins. See the
“DLP-A19 Install Alarm Wires on the Backplane” task on page 17-22 for more information.
Step 2 In node view, double-click the AIC card to display it in card view.
Step 3 Click the Provisioning > External Alarms tabs.
Step 4 Modify any of the following fields for each external device wired to the ONS 15454 backplane. For
definitions of these fields, see the “NTP-A32 Provision External Alarms and Controls on the Alarm
Interface Controller” procedure on page 7-9.
• Enabled
• Alarm Type
• Severity
• Virtual Wire
• Raised When
• Description
Step 5 To provision additional devices, complete Step 4 for each additional device.
Step 6 Click Apply.
Step 7 Return to your originating procedure (NTP).
DLP-A174 Change External Controls Using the AIC Card
Step 1 Verify the external control relays to the ENVIR ALARMS OUT backplane pins. See the “DLP-A19
Install Alarm Wires on the Backplane” task on page 17-22 for more information.
Step 2 In node view, double-click the AIC card to display it in card view.
Purpose This task changes external alarm settings on the Alarm Interface Controller
(AIC) card.
Tools/Equipment None
Prerequisite Procedures DLP-A60 Log into CTC, page 17-66
Required/As Needed As needed
Onsite/Remote Onsite or remote
Security Level Provisioning or higher
Purpose This task changes external control settings on the AIC card.
Tools/Equipment None
Prerequisite Procedures DLP-A60 Log into CTC, page 17-66
Required/As Needed As needed
Onsite/Remote Onsite or remote
Security Level Provisioning or higher