AKD User Guide | BODE Parameters
BODE.VFLIMIT
General Information
Type R/W Parameter
Description
Sets the velocity fault duration limit (seconds) for the BODE.MODE 5 sta-
bility test
Units s
Range 0.001 to 60.000
Default Value 0
Data Type Decimal
See Also
BODE.MODE, BODE.MODETIMER, BODE.IFLIMIT, BODE.I-
FTHRESH, BODE.VFTHRESH
Start Version M_01-02-10-000
Description
When BODE.MODE is set to 5, the firmware monitors the drive feedback velocity VL.FB. When VL.FB goes
above BODE.VFTHRESH, an internal counter records the length of time VL.FB was above BODE.VFTHRESH.
If the internal counter reaches BODE.VFLIMIT, Fault 133 Instability during Autotune will be generated.
The smaller BODE.VFLIMIT, the quicker Fault 133 will be generated when VL.FB exceeds BODE.VFLIMIT.
Example
Set BODE.VFTHRESH to 10 RPM:
-->BODE.VFTHRESH 10
Set BODE.VFLIMIT to 0.500 seconds
-->BODE.VFLIMIT 0.5
Set BODE.MODE to 5 to enable stability detection
-->BODE.MODE 5
Related Topics
14.3 Using the Autotuner
14.3.4 Using the Autotuner: Advanced