IL.LIMITN
General Information
Type NV Parameter
Description Sets the negative user (application-specific) current limit.
Units A
Range Negative drive peak current (DRV.IPEAK) to 0 A
Default Value Negative drive peak current (DRV.IPEAK)
Data Type Float
See Also IL.LIMITP
Start Version M_01-00-00-000
Fieldbus Index/Subindex Object Start Version
EtherCAT COE
and CANopen
356Fh/0 M_01-00-00-000
Modbus 460 M_01-03-00-000
Description
This parameter sets the negative user limit clamp value of the torqueproducing q-component current command
(IL.CMD ). The current command is additionally limited by the motor peak current setting (MOTOR.IPEAK) and
by the present value of the foldback I²t peak motor current protection.
Related Topics
11.3 Current Loop
AKD User Guide | IL Parameters