IL.CMDU
General Information
Type R/W Parameter
Description Sets the user current command.
Units Arms
Range
[Maximum of user negative current limit (IL.LIMITN) and negative motor
peak current (MOTOR.IPEAK)] to [minimum of user positive current limit
(IL.LIMITP) and motor peak current (MOTOR.IPEAK)]
Default Value 0 Arms
Data Type Float
See Also DRV.IPEAK, DRV.OPMODE,DRV.CMDSOURCE
Start Version M_01-00-00-000
Fieldbus Index/Subindex Object Start Version
Modbus 430 M_01-03-00-000
Description
This parameter sets the user current command value.
The current command value, which is provided to the current loop (IL.CMD), can be limited further using a param-
eter setting or I
2
t calculation. IL.CMDU is limited also by motor peak current, IL.LIMITN and IL.LIMITP.
Related Topics
11.3 Current Loop
AKD User Guide | IL Parameters
Kollmorgen | December 2010 461

Table of Contents

Other manuals for Kollmorgen AKD series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kollmorgen AKD series and is the answer not in the manual?

Kollmorgen AKD series Specifications

General IconGeneral
Continuous CurrentUp to 180 A
Control ModesPosition, Velocity, Torque
Communication InterfacesEtherCAT, CANopen, Modbus TCP/IP
Feedback OptionsResolver, Encoder
Safety FeaturesSafe Torque Off (STO), Safe Stop 1 (SS1)
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short Circuit, Overtemperature
Switching Frequency8 kHz, 16 kHz
Ambient Temperature0°C to 40°C
Operating Temperature0 - 40 °C (derating may apply)
Humidity5% to 95% non-condensing