AKD User Guide | VBUS Parameters
VBUS.UVMODE
General Information
Type N/V Parameter
Description Indicates undervoltage (UV) mode.
Units N/A
Range 0 to 1
Default Value 1
Data Type Boolean
See Also N/A
Start Version M_0-0-37
Fieldbus Index/Subindex Object Start Version
Modbus 802 M_01-03-00-000
Description
This parameter indicates undervoltage (UV) mode.
When VBUS.UVMODE - 0, an undervoltage fault is issued whenever the DC bus goes below the undervoltage
threshold.
When VBUS.UVMODE = 1, an undervoltage fault is issued whenever the DC bus goes below the
under voltage threshold and the controller attempts to enable the drive (software or hardware enable).
Related Topics
7.2 Regeneration
618 Kollmorgen | December 2010