Fig. 3-75 2800 – Parameter manager
- 2800 -
Function diagram
87654321
fp_2800_54_eng.vsd
DO: SERVO, VECTOR
S120/S150/G130/G150SI Basic Functions - Parameter manager
Change safety parameters
p9601 = 0
[2810.3]
SI password input
p9761
Reset safety parameters
Inhibit safety functions
x
r9780 CU/r9880 MM
06.03.12 V04.07.00
p9801 = 0
[2810.3]
All safety parameters
can be reset to the
factory settings via
p0970, p3900
Activates all
password-protected
safety parameters
SI password new
p9762
SI ackn password
p9763
Safety commissioning mode
[2802.1], [2804.1], [2804.3], [2810.3]
--> STO is selected
Safety parameterizing enable
y
Effective password
=
Enter password
=
SET
y = x
Safety parameters
p9601 ... p9899
are valid
<1> The target checksum must be equal to the actual checksum.
<2> Some parameters require a POWER ON.
p9899
SI set_checksum MM
r9898
SI act_checksum MM
SI set_checksum CU
p9799
SI act_checksum CU
r9798
p0010 95
Exit safety
commissioning mode
Checksum check
for safety
parameters
&
& &
Safety Integrated commissioning
p0010 = 95
<2>
<1>
<1>
=
=