3 Function diagrams
3.10 Safety Integrated Extended Functions
Fig. 3-82 2818 – Parameter manager
- 2818 -
Function diagram
87654321
fp_2818_54_eng.vsd
DO: SERVO, VECTOR
S120/S150/G130/G150SI Extended Functions - Parameter manager
Changing safety parameters
SI password input
p9761
Resetting safety parameters
Disabling Safety functions
x
p10000 (12.00 ms)
31.01.14 V04.07.00
Safety parameter
p9300 ... p9399
p9500 ... p9599
can be reset to
factory settings via
p0970, p3900
Safety parameter
p9300 ... p9399
p9500 ... p9599
can be changed
SI password new
p9762
SI ackn password
p9763
Safety parameterization enable
y
Effective password
=
Password entry
=
SET
y = x
Safety parameters
p9300  p9399
p9500 ... p9599
are valid after
POWER ON
p9399
SI ref CRC MM
r9398
SI act CRC MM
SI Mtn ref CRC
p9729
SI Mtn act CRC
r9728
p0010
95
Quit Safety commissioning mode
Checksum check
for
Safety parameters
& &
Safety Integrated commissioning
p0010 = 95
SI enable fct CU
p9601 = 0
SI enable fct MM
p9801 = 0
SI Mtn enable MM
p9301 = 0
SI Mtn enable fct
p9501 = 0
=
=
Commissioning mode active (p0010 = 95)
r10054.0