3 Function diagrams
3.18 Diagnostics
SINAMICS G130/G150
1216 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-165 8075 – Faults/alarms configuration
- 8075 -
Function diagram
87654321
fp_8075_51_eng.vsd
DO: All objects
SINAMICS
22.01.14 V04.07.00
Diagnostics - Faults/alarms configuration
0. F_no F response
1. F_no F response
19. F_no F response
[0]
[1]
[19]
Changing the fault response <1>
Fault response
Fault response
Fault response
[0]
[1]
[19]
0 = NONE
1 = OFF1
2 = OFF2
3 = OFF3
0. Fault_no ackn_mode
1. Fault_no ackn_mode
19. Fault_no ackn_mode
[0]
[1]
[19]
Changing the acknowledge mode <1>
Acknowledge mode
Acknowledge mode
Acknowledge mode
[0]
[1]
[19]
1 = Acknowledgement is only possible using POWER ON
2 = Acknowledgement IMMEDIATELY after the cause has been removed.
<1> The fault response, acknowledge mode and message type for all faults and alarms are set to meaningful default values in the factory setting.
Changes that may be required are only possible in specific value ranges specified by SIEMENS.
When the message type is changed, the supplementary information is tranferred from fault value r0949 to alarm value r2124 and vice versa.
0. Fault/alarm code
1. Fault/alarm code
19. Fault/alarm code
[0]
[1]
[19]
Changing the message type (fault <==> alarm) <1>
Fault/alarm type
Fault/alarm type
Fault/alarm type
[0]
[1]
[19]
1 = Fault (F)
2 = Alarm (A)
p2100 p2101 p2118 p2119
p2126 p2127
5 = STOP2
6 = IASC/DCBRK
Background
3 = Acknowledge only when the PULSES ARE INHIBITED.
7 = ENCODER (p0491)
3 = No message(N)