3 Function diagrams
3.19 Data sets
SINAMICS G130/G150
1220 List Manual (LH2), 04/2014, A5E03263479A
Fig. 3-168 8565 – Drive Data Sets (DDS)
- 8565 -
Function diagram
87654321
fp_8565_54_eng.vsd
DO: SERVO, VECTOR, TM41
S120/S150/G130/G150
03.07.13 V04.07.00
Data sets - Drive Data Sets (DDS)
Not relevant
Drive n
(0)
Select DDS bit 0
p0820[C]
(0)
Select DDS bit 1
p0821[C]
(0)
Select DDS bit 2
p0822[C]
(0)
Select DDS bit 3
p0823[C]
Copy DDS, source
p0819[0] (0)
Drive 2
Drive 1
Copy DDS, target
p0819[1] (1)
Copy DDS, start
p0819[2] (0)
DDS31
DDS number
p0180 (1)
DDS1
DDS0
(0)
Select DDS bit 4
p0824[C]
DDS selected
r0837.0
r0837
r0837.3
DDS effective
r0051.0
r0051
r0051.4
r0837.2
r0837.1
r0051.3
r0051.2
r0051.1
A07530 "Drive data set does not exist"
r0837.4
r0049
r0049[0] Motor data set MDS effective
r0049[1] Encoder 1 encoder data set EDS effective
r0049[2] Encoder 2 encoder data set EDS effective
r0049[3] Encoder 3 encoder data set EDS effective
r0838
r0838[0] Motor data set MDS selected
r0049[1] Encoder 1 encoder data set EDS selected
r0838[2] Encoder 2 encoder data set EDS selected
r0838[3] Encoder 3 encoder data set EDS selected
MDS (Motor Data Set)
EDS (Encoder Data Set)
DDS (Drive Data Set)
p0186[0...n] (MDS number)
p0187[0...n] (enc 1 EDS number)
p0188[0...n] (enc 2 EDS number)
p0189[0...n] (enc 3 EDS number)
<1>
<1> A BICO interconnection to a parameter which is part of a drive data set always influences the currently effective data set.
<2> Only for SINAMICS S120/S150.
<2>
<2>
<2>
<2>
<2>
<2>