10
11
NO0
NO1
13
NO3
12
NO2
14
R0...3
15
NO4
16
NO5
17
NO6
18
NO7
19
R4...7
20
L+
120 V AC/
240 V AC
~
120 V AC/
240 V AC
~
L
N
L
N
Fig. 14: Connection of 100-240 VAC actuators
NOTICE!
Risk of damaging the I/O Module!
The outputs are not protected against short circuit and overload.
Never short-circuit or overload the outputs.
Never connect inductive loads without an external suppression against
voltage peaks due to inductive kickback.
Never connect voltages > 240 V. All outputs must be supplied from the
same phase.
Use an external 5 A fast protection fuse for the outputs.
CPU or
Bus Module
DO571
24 V DC
+
20
L+ / UP
I/OBus
M / ZP
L+
Fig. 15: Power supply - the negative connection is realized via the I/O bus
Device Specifications
I/O Modules > Digital I/O Modules
2019/04/17 3ADR010121, 13, en_US 245