The assignment of the terminals:
Terminal Signal Description
10 --- Reserved
11 --- Reserved
12 --- Reserved
13 O0U+ Voltage output of channel 0
14 O0I+ Current output of channel 0
15 O1U+ Voltage output of channel 1
16 O1I+ Current output of channel 1
17 O01- Negative pole of channels O0 and O1
18 SG Signal ground
19 L+ Process voltage L+ (24 VDC)
20 M Process voltage M (0 VDC)
The internal power supply voltage for the module's circuitry is carried out via the I/O bus (pro-
vided by a bus module or a CPU). Thus, the current consumption from 24 VDC power supply at
the terminals UP/L+ and ZP/M of the CPU/bus module increases by 5 mA per AO561.
The external power supply connection is carried out via the L+ (+24 VDC) and the M (0 VDC)
terminals. The M terminal is electrically interconnected to the M/ZP terminal of the CPU/bus
module.
NOTICE!
Risk of imprecise and faulty measurements!
Analog signals may be distorted seriously by external electromagnetic influ-
ences.
Use shielded wires when wiring analog signal sources. The cable shield must
be grounded at both ends of the cable. Provide a potential equalisation of a low
resistance to avoid high potential differences between different parts of the
plant.
Device Specifications
I/O Modules > Analog I/O Modules
2019/04/173ADR010121, 13, en_US430