Fig. 3-23 2425 – STW1_BM control word, metal industry interconnection
- 2425 -
Function diagram
87654321
fp_2425_54_eng.vsd
DO: SERVO, VECTOR
S120/S150/G130/G150
27.06.13 V04.07.00
PROFIdrive - STW1_BM control word, metal industry interconnection
STW1.0
STW1.1
STW1.2
STW1.3
STW1.4
STW1.5
STW1.6
STW1.8
STW1.9
STW1.7
STW1.10
p0848[0] = r2090.2
p2816[0] = r2090.3
p1140[0] = r2090.4
p1141[0] = r2090.5
p1142[0] = r2090.6
p2103[0] = r2090.7
-
-
p0854[0] = r2090.10
p0840[0] = r2090.0
p0844[0] = r2090.1
0 = OFF (OFF1)
= ON
0 = OFF2 (immediate pulse suppression and switch on inhibit)
1 = No OFF2 (enable is possible)
0 = OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switch on inhibit)
1 = No OFF3 (enable is possible)
0 = Inhibit operation
1 = Enable operation
0 = Inhibit ramp-function generator
1 = Operating condition
0 = Stop the ramp-function generator
1 = Enable the ramp-function generator
0 = Inhibit setpoint = 0
1 = Enable setpoint
= Acknowledge faults
Reserved
Reserved
1 = Control via PLC
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2501.3]
[2546.1]
-
-
[2501.3]
[2501.3]
[2501.3]
Signal targets for STW1_BM
[2610]
[2634.3]
[3060] [3070] [3080]
[3060] [3070]
[3060] [3070] [3080]
[8060]
-
-
[2501]
[2610]
[2610]
-
-
-
-
-
-
-
-
-
-
-
Signal
Interconnection
parameters
Meaning
[Function diagram]
internal control word
[Function diagram]
signal target
Inverted
<2>
<1>
PROFIdrive sampling time
<1> Used in telegram 220.
<2> STW1.10 must be set to ensure that the drive object accepts the process data (PZD).
<3> Interconnection is not disabled.
STW1.11 Reserved -- - -
STW1.12 Reserved -- -
STW1.13 Reserved -- -
STW1.14 Reserved -- -
STW1.15 Reserved -- -
<3>
<3>
<3>
<3>
<3>
<3>
<3>
<3>