1091
3 Function diagrams
3.5 PROFIdrive
Fig. 3-53 2497 – A_DIGITAL interconnection
- 2497 -
Function diagram
87654321
fp_2497_54_eng.vsd
DO: CU_G, CU_S
S120/S150/G130/G150
27.06.13 V04.07.00
PROFIdrive - A_DIGITAL interconnection
Signal targets for A_DIGITAL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
p0740 = r2091.2
p0742 = r2091.4
p0743 = r2091.5
p0744 = r2091.6
p0745 = r2091.7
p0739 = r2091.1
---
Inverted
[Function diagram]
signal target
[Function diagram]
internal status word
Interconnection
parameters
-
-
-
-
-
-
-
-
-
- -
p0738 = r2091.0
-
p0741 = r2091.3
A_DIGITAL.1
A_DIGITAL.2
A_DIGITAL.3
A_DIGITAL.4
A_DIGITAL.5
A_DIGITAL.6
A_DIGITAL.8
A_DIGITAL.9
A_DIGITAL.11
A_DIGITAL.12
A_DIGITAL.13
A_DIGITAL.14
A_DIGITAL.15
A_DIGITAL.7
A_DIGITAL.10
A_DIGITAL.0
Signal
Digital output 12 (DI/DO 12)
Digital output 15 (DI/DO 15)
Reserved
Reserved
Digital output 14 (DI/DO 14)
Digital output 13 (DI/DO 13)
Digital output 11 (DI/DO 11)
Digital output 10 (DI/DO 10)
Digital output 9 (DI/DO 9)
Reserved
Reserved
Reserved
Reserved
Reserved
Digital output 8 (DI/DO 8)
Meaning
Reserved
-
-
-
-
<3> Pre-assignment, can be freely changed.
<3>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2>
<2> Can be set via p0728 as input (DI) or output (DO).<1> Used in telegrams 390 to 396.
<1>
PROFIdrive sampling time