Home
Toshiba
Storage
GR200 Series
Toshiba GR200 Series User Manual
5
of 1
of 1 rating
1770 pages
Give review
Manual
Specs
To Next Page
To Next Page
Loading...
6F2
S19
14
(
Re
v
.
0.
4
9
)
No
tice
:
G
RL20
0
m
a
nu
a
l
i
s
i
s
s
u
e
d
fo
r
‘
0
3
3
’
,
a
nd
‘
0
3
7
’
s
o
ftw
a
r
e
c
o
d
e
,
w
hi
c
h
y
o
u
c
a
n
i
d
e
nti
fy
a
t
the
’
S,
G&
T
po
s
i
ti
o
ns
’
o
n
S
o
ft
w
a
r
e
n
a
m
e
pl
a
te
.
G
RL2
0
0
-
-
-
S
,
G
,
a
nd
T po
s
i
ti
o
ns
T
O
S
H
I
B
A
E
N
E
R
G
Y
S
Y
S
T
E
M
S
&
S
O
L
U
T
I
O
N
S
C
O
R
P
O
R
A
T
I
ON
Instr
uction manual
Line dif
ferential Pr
otection IED
GR200 series (GRL200)
2
Table of Contents
1 Introduction
24
1.1 Protection functions
25
1.1.1 Purposes of the protection
25
1.1.2 Requirements in the protection functions
25
(i) Selectivity
25
(ii) Speediness
26
(iii) Reliability
27
1.1.3 Behavior of backup protections
27
(i) Protection for the line
27
(ii) Coordination between the main and the backup protections
28
(iii) Types of the backup protections
28
(iii)-1 Remote backup protection (Retarded backup protection)
29
(iii)-2 Local backup protection (High-speed backup protection):
29
1.1.4 Concepts of current differential protection (DIF) function
29
1.1.5 Concepts of distance protection (ZS/ZG) function
29
(i) The reach of the zone1 element
30
(ii) Measuring error and its influence
30
(iii) Detection of power swing and out-of-step
31
1.1.6 Concepts of carrier command protection (DISCAR/DEFCAR) function
33
(i) DISCAR Command protection by the distance (ZS/ZG) protection
33
(ii) DEFCAR command protection by the earth fault (EF) protection
33
(iii) Operation with autoreclosing (ARC)
33
1.1.7 Tripping CB by the protection functions
33
1.1.8 Autoreclosing CB (ARC) after the operation of the protection functions
34
1.1.9 Conventional applications
34
1.2 Control
35
1.2.1 General control function
35
1.2.2 Control and monitoring application
35
1.3 Monitoring and metering functions
36
1.4 Hardware overview
37
1.5 Symbols used in logical diagrams
38
(i) Relay element, signal-monitoring point, PLC connection point, and Mapping point
38
(ii) Timer symbol
39
(iii) Logic symbol
40
(iv) Flip-flop symbol
41
(v) Scheme switch
41
1.6 Abbreviation
42
1.7 Function Block (FB), Function ID, Signal number (Data ID)
44
(i) Signal symbols
44
(ii) Data length (bit length of Data ID)
44
2 Relay application
46
2.1 Current differential protection for the line
47
2.2 Segregated-phase current differential protection function (DIFL)
48
2.2.1 Differential protection characteristics (DIFL)
49
(i) Characteristic of differential (Id) and restraint (Ir) current plane
49
(ii) Characteristic of Inflowing and Outflowing currents plane
50
(iii) Trip delay timer in main logic
51
(iv) Trip mode
53
(iv)-1 TRIP commands for opening the CB poles
53
(iv)-2 TRIP commands during CTF
53
(v) Switch for DIFL operation
53
(vi) Setting for autoreclose function
53
(vii) Blocking trip issuing by communication failure supervision
54
(viii) Blocking trip issuing by by PLC connection
54
2.2.2 Check relays characteristics (OCs and UVs)
55
(i) Current change detection element (OCD-DIFL)
56
(ii) Over-current detection (OC-DIFL)
56
(iii) Under-voltage element (UV-DIFL)
56
(iv) Under-voltage element for phase-to-phase (UVS-DIFL)
57
(v) Under-voltage change detection element (UVD-DIFL)
57
(vi) Check relays activation
57
2.2.3 CT circuit-failure detection (DIFL-CTF)
57
2.2.4 Charging-current compensation (DIFL-Ic)
58
2.2.5 Differential current monitor (DIFL-IDSV)
60
2.2.6 Setting
61
2.2.7 Data ID
62
2.3 Zero-sequence current differential protection (DIFGL)
64
2.3.1 Differential protection characteristics (DIFGL)
64
(i) Ir-Id plane for DIFGL function
64
(ii) Inflow current (Iin) and Outflow current (Iout) plain for DIFGL function
65
(iii) Trip delay timer in main logic
66
(iv) Trip mode
67
(v) Operation switch
67
(vi) Setting for autoreclose function
67
(vii) Block of issuing a trip signal
68
(viii) Specializing in micro earth faults
68
2.3.2 Check relay characteristic (EFD)
69
(i) Earth-fault-current-change detection element (EFD-DIFGL)
69
(ii) Check relay activation
70
2.3.3 CT circuit-failure detection (DIFGL-CTF)
70
2.3.4 Charging-current compensation (DIFGL-Ic)
71
(i) Setting for the compensation
71
(ii) Activation switch
71
2.4 CT saturation countermeasure in DIFL (CTsat in DIFL)
72
2.4.1 Stabilization for CT saturation owing to through-fault current
72
(i) Principle of operation
72
(ii) CT secondary current waveforms
74
2.4.2 Settings against CT saturation
75
(i) When Wide is applied in 1CB (Setting No.6)
75
(ii) When Normal is applied in 1CB (Settings No. 1 and 2)
75
(iii) Counter measure for 1.5CB (Setting No. 8)
75
2.4.3 Setting
77
2.5 Setting DIFL accounting for CT ratio/rating and fault currents
78
2.5.1 Nature of CT ratios matching
78
(i) DIFL setting for CT ratios being identical
78
(ii) DIFL setting for CT ratios being not identical
78
2.5.2 Nature of CT ratings matching
79
2.5.3 Nature for fault current setting
79
(i) Setting DIFL-I1 characteristic
79
(ii) Setting DIFL-I2 characteristic
80
(iii) Setting DIFGL-I characteristic
80
(iv) Setting DIFL-IDSV monitor
81
(v) Setting DIFL-IcC compensation
81
2.6 DIFL operations for 1.5CB arrangement
82
2.6.1 Through-fault-current encountered by DIF (TFC in DIFL and DIFGL)
82
(i) Operation of TFC countermeasure in DIFL
83
(i)-1 Sending DIFL operation signal for the opposite
83
(i)-2 Reception of DIFL-operation signal from the remote
84
(ii) Operation of TFC countermeasure in DIFLG
86
(ii)-1 Sending DIFGL operation signal for the opposite
86
(ii)-2 Reception of DIFGL-operation signal from the remote
87
2.6.2 Settings in TFC
90
2.6.3 Data IDs in TFC
90
2.6.4 Stub protected by DIFL (Stub-DIFL)
91
(i) DIFL operation at terminal-G
91
(ii) DIFL operation at terminal-H
92
2.6.5 Settings in Stub
93
2.6.6 Data ID in Stub
94
2.6.7 DIFL applied to double circuit line with a fault (Fault current outflowing)
95
2.7 DIFL applied to three-terminal line (RDIF and Fault current flowing)
96
2.7.1 Remote different trip
96
(i) RDIF operation relating to DIFL function
97
(i)-1 Sending local-DIFL-operation signal
97
(i)-2 Reception of remote-DIFL-operation signal
98
(ii) RDIF operation relating to DIFGL function
100
(ii)-1 Sending local-DIFGL-operation signal
100
(ii)-2 Reception of remote-DIFGL-operation signal
101
2.7.2 Setting
103
2.7.3 Data ID
103
2.7.4 Nature of outflowing current in case of internal fault
105
(i) Account of DIFL settings for a single line with outer loop
105
(ii) Account of DIFL settings for parallel lines
105
2.7.5 Nature of CT saturation in case of external fault
106
2.8 DIFL applied to protect the blind zone
107
2.9 Stub protection with overcurrent relay (STUB-OC)
109
2.9.1 Stub-OC characteristic
110
2.9.2 Scheme logic
110
2.9.3 Setting
112
2.9.4 Data ID
113
2.10 Distance protection (ZS/ZG)
114
2.10.1 Principle of distance measurement
115
(i) Phase-to-phase fault
115
(ii) Single-phase-earth fault
116
2.10.2 Equations in distance protection function
119
(i) Element equations for Mho characteristic
119
(ii) Element equations for offset Mho characteristic
120
(iii) Element equations for reactance characteristic
121
(iv) Element equations for blinder characteristic
123
(v) Element equations for directional characteristic
123
2.10.3 Element characteristic in distance relay
126
(i) Common characteristic of ZS and ZG
126
(i)-1 Mho characteristic
126
(i)-2 Quad characteristic
128
(i)-3 Number of zones
129
(i)-4 Selection of Forward, Reverse, or Non-directional for the respective zones
129
(i)-5 Function and classification of 6 zones
131
(i)-6 Charging current compensation
132
(ii) Special characteristic in ZS
133
(ii)-1 Overreach countermeasure
133
(ii)-2 Offset characteristics in ZS
134
(ii)-3 Operation of ZS for earth and multi-phase-faults
135
(iii) Special characteristic in ZG
135
(iii)-1 Earth fault compensation (Zero sequence current compensation)
135
(iii)-2 Operation of ZG for earth-faults and multi-phase faults
138
2.10.4 Common application for ZS and ZG
140
(i) Power swing block
140
(i)-1 Operation of power swing block (PSB)
140
(i)-2 Setting for blocking operation of Distance protection
144
(ii) Load encroachment
144
(iii) Fail safe function
145
(iv) Definite time delay operation
145
(v) Autoreclose initiation blocking
146
(vi) Zone 1 control
146
2.10.5 Command protection feature
147
(i) ZS command protection
147
(ii) ZG command protection
149
2.10.6 Extended application
152
(i) Switch-onto-fault (SOTF)
152
(ii) Blocking all phase-ground elements
152
(iii) Enhancing the detection of faulted-phases
152
(iii)-1 Enhances in Z1G, Z1XG & Z5G zones
153
(iii)-2 Enhances in Z2G, Z3G & Z4G zones
153
(iii)-3 Calculation in Z*G-CovCoeff
154
(iii)-4 Enhances in Z1S, Z1XS& Z5S zones
154
2.10.7 Scheme logic
155
(i) ZS logic
155
(ii) ZG logic
162
(ii)-1 Instantaneous and blocking TRIP commands
169
(ii)-1 TRIP commands for opening the CB poles
170
2.10.8 Tips to set the main/remote backup relays
171
(i) Setting for the primary line (Zone1)
171
(ii) Setting for adjacent lines (Zone2 serviced as a backup relay)
172
(iii) Setting for far adjacent lines (Zone3 serviced as a backup relay)
173
(iv) Setting for backward lines (Zones4 and 5 serviced as backup relays)
174
(v) Extra setting for the primary zone (Zone1X with autoreclosing)
174
2.10.9 Tips to set the distance zones for multi-terminal lines
175
(i) Setting for reverse zones (Zone4 served as a backup relay)
175
(ii) Setting for the primary zone (Zone1 and a junction)
175
(iii) Setting for the primary zone (Zone1 and a short tapped line)
176
2.10.10 ZS/ZG test
177
(i) ZS-Test.CTRL
177
(ii) ZS-Offset.CTRL
177
(iii) ZS-Test.XAngle, ZG-Test.XAngle
177
2.10.11 Setting
178
2.10.12 Data ID
194
2.11 Direct transfer trip (DTT)
203
2.11.1 Setting for the operation
204
2.11.2 Scheme logic
205
2.11.3 Setting
206
2.11.4 Data ID
206
2.12 Distance carrier command protection (DISCAR)
208
2.12.1 Permissive underreach protection (PUP)
209
(i) Application
209
(ii) Scheme logic
209
2.12.2 Permissive overreach protection (POP)
210
(i) Application
210
(ii) Operation of echo (ECHO) and week infeed trip (WKIT)
211
(iii) Countermeasure of current reversal (CRL)
211
(iv) Criterion of POP tripping
211
(v) Scheme logic
211
(vi) Delay of trip permission signal
213
2.12.3 Unblocking overreach protection (UOP)
213
(i) Operation of echo (ECHO) and week infeed trip (WKIT)
214
(ii) Countermeasure of current reversal (CRL)
214
(iii) Delay of trip block signal
214
(iv) Scheme logic
214
2.12.4 Blocking overreach protection (BOP)
215
(i) Countermeasure of current reversal (CRL)
216
(ii) Scheme logic
216
2.12.5 Protection for week infeed terminal
218
(i) ECHO function
218
(ii) WIKT function
219
2.12.6 Countermeasure for current reversal
220
2.12.7 Carrier signal reception
222
2.12.8 Setting
224
2.12.9 Data ID
225
2.13 Directional earth fault command protection (DEFCAR)
227
2.13.1 Permissive overreach protection (POP)
228
2.13.2 Unblocking overreach protection (UOP)
231
2.13.3 Blocking overreach protection (BOP)
231
2.13.4 Coordination with DISCAR protection
233
(i) DISCAR and DEFCAR signals being separated
233
(ii) DISCAR and DEFCAR signals being shared
233
2.13.5 Carrier signal reception
234
2.13.6 Setting
236
2.13.7 Data ID
237
2.14 Switch on to fault (SOTF-OC)
239
2.14.1 Scheme logic
240
2.14.2 Setting
242
2.14.3 Data ID
242
2.15 Overcurrent protection (OC)
243
2.15.1 Relay polarity
244
(i) Characteristic of non-directional OC
244
(ii) Characteristic of directional-OC element in the forward direction
244
(iii) Characteristic of directional OC in the reverse direction
247
2.15.2 Inverse time and definite time delay characteristic
247
(i) Operation principle
247
(i)-1 Dependent time characteristic (inverse time delay)
247
(i)-2 Definite time delay (independent time characteristic)
248
(ii) DT characteristic
249
(iii) IDMT characteristic
249
(iv) Operate time of IDMT
249
(v) Operate time of DT
251
(v)-1 Time characteristic
251
(v)-2 Instantaneous activation
251
(vi) Reset time of IDMT
251
(vii) Reset time of DT
253
(viii) Summary of OC operation
254
2.15.3 Threshold value for operation
254
2.15.4 Reset Ratio
254
2.15.5 Miscellaneous functions
254
(i) Trip mode
254
(ii) Blocking OC by ICD
255
(iii) Blocking OC by VTF
255
(iv) OC operation for auto-reclose
255
(v) Signal of OC trip
256
2.15.6 Scheme logic
256
2.15.7 Setting
258
2.15.8 Data ID
263
2.16 Earth fault protection (EF)
266
2.16.1 Relay polarity
267
(i) Characteristic of non-directional EF
267
(ii) Characteristic of directional-EF in the forward direction
267
(iii) Characteristic of directional EF in the reverse direction
269
2.16.2 Inverse time and definite time delay characteristic
269
(i) DT characteristic
269
(ii) IDMT characteristic
269
(iii) Operate time of IDMT
270
(iv) Operate time of DT
271
(iv)-1 Time characteristic
271
(iv)-2 Instantaneous activation
271
(v) Reset time for IDMT
271
(vi) Reset time of DT
274
(vii) Summary of EF operation
274
2.16.3 Threshold level for operation
274
2.16.4 Reset Ratio
274
2.16.5 Miscellaneous functions
274
(i) Blocking EF by ICD
275
(ii) Blocking EF by VTF
275
(iii) Blocking EF by CTF
275
(iv) EF operation for autoreclose
275
(v) Signal of EF trip
275
2.16.6 Scheme logic
275
2.16.7 Setting
277
2.16.8 Data ID
282
2.17 Negative sequence overcurrent protection (OCN)
284
2.17.1 Relay polarity
285
(i) Characteristic of a non-directional OCN
285
(ii) Characteristic of directional OCN in the forward
285
(iii) Characteristic of directional OCN in the reverse
287
2.17.2 Inverse time and definite time delay characteristic
287
(i) DT characteristic
287
(ii) IDMT characteristic
287
(iii) Operate time of IDMT
288
(iv) Operate time of DT
289
(iv)-1 Time characteristic
289
(iv)-2 Instantaneous activation
289
(v) Reset time of IDMT
289
(vi) Reset time of DT
292
(vii) Summary of OCN operation
292
2.17.3 Threshold value
292
2.17.4 Reset Ratio
292
2.17.5 Miscellaneous functions
292
(i) Harmonic detection
293
(ii) Blocking OCN by VTF
293
(iii) Blocking OCN by CTF
293
(iv) OCN operation for autoreclose
293
(v) Signal of OCN trip
293
2.17.6 Scheme logic
293
2.17.7 Setting
295
2.17.8 Data ID
300
2.18 Thermal overload function (THM)
302
2.18.1 Thermal state determination
303
2.18.2 Thermal characteristic
304
2.18.3 Scheme logic
305
2.18.4 Setting
306
2.18.5 Data ID
307
2.19 Broken conductor protection (BCD)
308
2.19.1 Equivalent circuit for a one-phase series fault
309
2.19.2 Characteristic and setting
311
2.19.3 Miscellaneous functions
311
(i) Harmonic detection function
311
(ii) Block operation of CTF for BCD
311
2.19.4 Scheme logic
312
2.19.5 Setting
312
2.19.6 Data ID
313
2.20 Circuit breaker fail protection (CBF)
314
2.20.1 CBF operation and its elements
315
2.20.2 Re-trip feature
315
2.20.3 Backup feature
316
2.20.4 Scheme logic
318
2.20.5 Operation timing
320
2.20.6 Setting
321
2.20.7 Data ID
322
2.21 Overvoltage protection for phase-to-neutral (OV)
324
2.21.1 Drop-off and pickup characteristic
325
2.21.2 Delay for the operation of the OV element
325
2.21.3 Time characteristic
325
(i) Definite time characteristic (DT)
325
(ii) Invers time characteristic (IDMT)
325
(ii)-1 Pick-up characteristic
325
(ii)-2 Reset feature
327
2.21.4 Miscellaneous functions
328
(i) OV operation blocked by the occurrence of VT failure
328
(ii) OV trip signal
328
(iii) Execution of OV function
328
2.21.5 Scheme logic
328
2.21.6 Setting list
330
2.21.7 Data ID
331
2.22 Overvoltage protection for phase-to-phase (OVS)
332
2.22.1 Drop-off and pickup setting
333
2.22.2 Delay for the operation of the OVS element
333
2.22.3 Time characteristic
333
(i) Definite time characteristic (DT)
333
(ii) Invers time characteristic (IDMT)
333
(ii)-1 Operation feature
333
(ii)-2 Reset feature
335
2.22.4 Miscellaneous functions
335
(i) OVS operation blocked by the occurrence of VT failure
335
(ii) Switch of OVS trip command
336
(iii) Execution of OVS function
336
2.22.5 Scheme logic
336
2.22.6 Setting list
337
2.22.7 Data ID
338
2.23 Earth fault overvoltage protection (OVG)
339
2.23.1 Drop-off and pickup setting
340
2.23.2 Delay of the operation of the OVG element
340
2.23.3 Time characteristic
340
(i) Definite time characteristic (DT)
340
(ii) Invers time delay (IDMT)
340
(ii)-1 Operation feature
341
(ii)-2 Reset feature
341
2.23.4 Miscellaneous functions
342
(i) OVG operation blocked by the occurrence of VT failure
342
(ii) Switch of OVG trip command
342
(iii) Execution of OVG function
343
2.23.5 Scheme logic
343
2.23.6 Setting
344
2.23.7 Data ID
345
2.24 Phase under-voltage protection (UV)
346
2.24.1 Drop-off and pick-up characteristic
347
2.24.2 Time characteristic
347
(i) Definite time characteristic (DT)
347
(i)-1 Setting pick-up operation
347
(i)-2 Setting drop-off operation
347
(ii) Inverse definite minimum time (IDMT) characteristic
347
(ii)-1 Setting pick-up operation
348
(ii)-2 Setting drop-off operation
348
2.24.3 Miscellaneous functions
349
(i) Blocking UV operation
349
(ii) UV trip signal
349
(iii) Operation of UV element
350
(iv) Under voltage test
350
2.24.4 Scheme logic
350
2.24.5 Setting
352
2.24.6 Data ID
353
2.25 Phase-to-phase under-voltage protection (UVS)
354
2.25.1 Drop-off and pick-up characteristic
355
2.25.2 Time characteristic
355
(i) Definite time characteristic (DT)
355
(i)-1 Setting pick-up operation
355
(i)-2 Setting drop-off operation
355
(ii) Inverse definite minimum time (IDMT) characteristic
355
(ii)-1 Pick-up characteristic
356
(ii)-2 Drop-off characteristic
356
2.25.3 Miscellaneous functions
357
(i) Block of UVS operation
357
(ii) UVS trip signal
358
(iii) Operation of UVS function
358
(iv) Under voltage test
358
2.25.4 Scheme logic
358
2.25.5 Setting
360
2.25.6 Data ID
361
2.26 Frequency protection (FRQ/DFRQ)
363
2.26.1 FRQ features and characteristics
364
(i) UF/OF characteristic
364
(ii) Enabling FRQ function
364
(iii) FRQ trip signal
365
(iv) UF/OF scheme logic
365
2.26.2 DFRQ features and characteristics
366
(i) RISE/DOWN characteristic
366
(ii) Enabling DFRQ function
366
(iii) DFRQ trip signal
366
(iv) DFRQ scheme logic
367
2.26.3 Setting
368
2.26.4 Data ID
370
2.27 Out of step tripping by voltage (OSTV)
373
2.27.1 Operation characteristic
374
2.27.2 Scheme logic and settings
376
2.27.3 Setting
377
2.27.4 Data ID
378
2.28 Inrush current detection function (ICD)
379
2.28.1 Operation and characteristic
380
2.28.2 Scheme logic
380
2.28.3 Setting
381
2.28.4 Data ID
381
2.29 Fail safe (FS)
382
2.29.1 Overcurrent element (OCFS)
383
2.29.2 Phase current change detector element (OCDFS)
383
2.29.3 Earth fault current element (EFFS)
383
2.29.4 Multi-level overcurrent elements (OCMFS)
384
(i) Characteristic of OCMFS
384
(ii) Setting of OCMF
385
2.29.5 Under-voltage element for phase-to-earth (UVFS)
385
2.29.6 Under-voltage element for phase-to-phase (UVSFS)
385
2.29.7 Under-voltage change detection element (DUVFS)
385
2.29.8 Scheme logic
386
2.29.9 Setting
388
2.29.10 Data ID list
389
2.30 VT failure detection (VTF)
390
2.30.1 VTF features
391
(i) Phase-to-earth under voltage element (UVVTF)
391
(ii) Earth fault overcurrent element (EFVTF)
391
(iii) Earth fault overvoltage element (OVGVTF)
391
(iv) Detection criterion for the VTF1
391
(v) Detection criterion for the VTF2
391
2.30.2 Operation for the VTF function
391
2.30.3 VTF Logic
392
2.30.4 Setting
394
2.30.5 Data ID
395
2.31 CT failure detection (CTF)
396
2.31.1 CTF features
397
(i) Earth fault overcurrent element (EFCTF)
397
(ii) Earth fault overvoltage element (OVGCTF)
397
(iii) Detection criterion (CTF_DETECT)
397
2.31.2 Operation for the CTF function
397
2.31.3 Scheme logic
397
2.31.4 Setting
399
2.31.5 Data ID
400
2.32 Multi-end fault locator (FL-A and FL-Z)
401
2.32.1 FL calculation with data at a local-terminal and remote-terminals
402
(i) Calculation Principle
403
(i)-1 Calculation on two-terminal application
403
(i)-2 Calculation on three-terminal application
403
(i)-3 Equations by symmetrical components
405
(ii) Data recording trigger and calculation trigger
406
(ii)-1 Trigger signal for data recording
407
(ii)-2 Trigger signal for FL calculation
407
(iii) Calculation error
407
(iii)-1 Calculation error in two-terminal-ends operation
408
(iii)-2 Calculation error in three-terminal-ends operation
408
2.32.2 FL calculation with data at a local-terminal only
409
(i) Calculation principle for phase-to-phase fault
409
(i)-1 Equations for the calculation in the case of phase-b-to-phase-c fault
409
(i)-2 Compensation for long line
410
(ii) Calculation principle for earth fault
410
(ii)-1 Equations
410
(ii)-2 Compensation
412
(iii) Data recording trigger and calculation trigger
412
(iii)-1 Trigger signal for Data recording
413
(iii)-2 Trigger signal for FL calculation
414
(iv) Calculation error
415
2.32.3 Selection of calculation results
415
2.32.4 Screen of FL output
416
(i) Fault determination in kilometer or mile
416
(ii) Fault determination in percentage
417
(ii)-1 Fault A arises on the line GJ
417
(ii)-2 Fault B arises on the line JH
417
(iii) Fault section information
417
(iv) Detail information
418
2.32.5 Preparation and consideration of setting
419
(i) Setting in each Line_element when three-terminal being applied
419
(ii) Setting in Line1_Element when two-terminal being applied
419
(iii) Setting for a signle IED configulation
419
(iv) Computation of impedance when variation being found in respective phases
419
(v) Computation of impedance when imbalance being found
420
2.32.6 Setting procedure
421
(i) FL execution
421
(ii) FL direction
421
(iii) Selection of either Matrix or Symmetrical component; and impedance settings
421
(iii)-1 Impedance setting in Matrix components
422
(iii)-2 Impedance setting in Symmetrical components
422
(iv) Compensation setting for earth fault for parallel lines
423
(v) Setting of the unit of length/distance
424
(vi) Setting of compensation factor
424
(vii) Computation for overreaching
424
2.32.7 Setting
425
2.32.8 Data ID
427
2.33 Trip circuit (TRC)
428
2.33.1 Command for tripping CB and signal to block reclosing CB#1/CB#2
431
2.33.2 Recording identifiers for respective fault types
434
2.33.3 Scheme logic
435
(i) Trip-signal collection
435
(ii) General-trip-signal production
435
(ii)-1 Acquisition of fail-safe signal provided externally
436
(ii)-2 Acquisition of external trip command
436
(ii)-3 Provision of trigger signals to Recording functions
437
(ii)-4 Provision for distance relay
437
(iii) CB trip signal production
437
(iii)-1 CB trip signals for 1CB system
437
(iii)-2 CBs trip signals for 1.5CB system
437
(iv) Sub-signal generation
437
(v) Alarm-signal generation
438
2.33.4 Setting
440
2.33.5 Data ID
441
2.34 Autoreclose (ARC)
443
2.34.1 Overview
444
(i) Breaker system
444
(ii) Reclosing modes in 1CB and 1.5CB
445
(ii)-1 Single-phase auto reclose (Setting [ARC1-MODE]=SPAR)
445
(ii)-2 Three-phase auto reclose (Setting [ARC1-MODE]=TPAR)
445
(ii)-3 Single- and three-phase auto reclose (Setting [ARC1-MODE]=SPAR&TPAR)
446
(ii)-4 Setting selection about SPAR and TPAR modes
446
(iii) Reclosing mode in parallel lines (Setting [ARC1-MODE]=MPAR)
446
(iv) User configurable autoreclose (Setting [ARC1-MODE]=Original)
447
(v) Number of reclosing shots
447
(v)-1 Single-shot autoreclose (Setting [ARC-NUM]=S1 in 1CB)
447
(v)-2 Multi-shot autoreclose (Setting [ARC-NUM]=S2/S3/S4/S5 in 1CB)
447
(v)-3 Signle-shot autoreclose (Setting [ARC-NUM]=S1 in 1.5CB)
447
(vi) Operation failure in tripping CB
447
(vii) Final trip stage
447
2.34.2 Terminology
449
(i) Relay operation period
449
(ii) Temporary/transient/Arc fault
449
(iii) Arcing time of CB
449
(iv) Permanent fault (Signal ‘ARC1 FT’)
449
(v) Signal shot scheme (Signal ‘ARC1 SHOT1’)
449
(vi) Multi shot scheme (Signals ‘ARC1 SHOT2–5’)
449
(vii) Dead time (Delay timers TTPAR† and TD_MS2–5)
450
(viii) Pulse width of ‘ARC1 CLOSE COMMAND’ (Setting TCCW1)
450
(ix) Final trip stage to abandon CB reclosure (Signal ‘ARC1 FT’ and setting TRR1, TRR_MS2–5)
450
(x) Reset for tripping failure (Signal ‘ARC1 RESET’ and setting TRESET)
450
(xi) Decision time for successful operation or failure (Setting TARCSUC and signals ‘ARC1 CLOSE SUCCESS’, ‘ARC1 CLOSE FAIL’, ‘ARC1 SHOT RS’)
451
(xi)-1 Scheme switch [ARC-SucChk]=On
451
(xi)-2 Scheme switch [ARC-SucChk]=Off
451
(xii) Progress of ARC operation (Signals ‘ARC1 IN-PROG’ and others)
451
(xii)-1 Entire ARC progress for all shots (signal ‘ARC1 IN-PROG’)
451
(xii)-2 Respective progress for respective shots (signal ‘ARC1-S* IN-PROG/OR’)
451
(xii)-3 Trigger for the ARC operation (signal ‘ARC_START’)
452
(xii)-4 Tripped phases (signals ‘TRIP-ANYPH’, ‘TRIP-1PH’, ‘TRIP-MPH’, ‘TRIP-3PH’)
452
(xiii) Reclaim timer (Setting ‘TREADY’)
452
(xiv) CB bridge (Signal ‘CB1_BRIDGE’)
452
(xv) Condition logic (Signals ‘ARC1_SPAR_COND’, ‘ARC1_TPAR_COND’)
453
(xvi) Link judgment (setting MPAR-MODE and signals ‘MPAR_LINK’)
453
2.34.3 Function block diagram
454
(i) SPAR mode
455
(ii) TPAR mode
457
(iii) SPAR and TPAR mode
459
(iv) MPAR mode
461
2.34.4 Timing diagram
463
(i) Single shot scheme for an Arcing fault (Shot1 for CB#1 and successful operation in TPAR mode)
463
(ii) Single shot scheme for an Arcing fault; CB#1 fails to reclose
463
(iii) Single shot scheme for Permanent fault
464
(iv) Single shot scheme for an Arcing fault; fault removed by a backup CB
465
(v) Multi shot scheme for Permanent fault
465
2.34.5 Autoreclosing logics
466
(i) Setting logic for ARC1 mode – setting (ARC1-MODE)
466
(ii) Setting logic for ARC2 mode – setting (ARC2-MODE)
468
(iii) Setting logic for shot number – setting (ARC-NUM)
469
(iv) Start logic – setting (FT-3P FAULT)
470
(v) Initiation logic – setting (TREADY1, TRESET)
472
(vi) Shot counter- setting (SHOTNUM-TEST)
474
(vii) Condition logic – setting (TEVLV)
475
(viii) SPAR logic – settings (TSPAR1, TRR1)
476
(ix) TPAR logic – settings (TTPAR1, TRR1)
477
(x) SPAR+TPAR logic – settings (TSPAR1,TTPAR1,and TRR1)
478
(xi) Shot2 to Shot5 for CB#1 –settings (TD_MS2, TRR2 and others)
479
(xii) Issuing close command – setting (TCCW1)
480
(xiii) Success check logic – settings (TARCSUC, ARC-SucChk)
481
(xiv) Reclosing sequence for two CBs system– setting (ARC-ORDER)
482
(xv) MPAR logic – settings (TMPAR, ARC-MANOLK, MPAR-MODE)
483
(xv)-1 Settings [ARC-MANOLK]=FT/TPAR/SPAR&TPAR in [MPAR-MODE]=M2
486
(xv)-2 Settings [ARC-MANOLK]=FT/TPAR/SPAR&TPAR in [MPAR-MODE]=M3
487
2.34.6 Setting
490
2.34.7 Data ID
492
2.35 Voltage check for autoreclose (VCHK)
498
2.35.1 VCHK1 for 1CB system
499
(i) Characteristic and elements
499
(ii) Voltage condition and check zone
499
2.35.2 VCHK1 and VCHK2 for 1.5CB system
500
(i) Characteristic and elements
500
(ii) Voltage condition and check zone
500
2.35.3 Scheme for synchronism
501
(i) Voltage magnitudes
502
(ii) Voltage difference
502
(iii) Frequency difference
503
(iv) Phase angle difference
503
(v) Notice and tips
503
2.35.4 VCHK1 setting for 1CB system
506
(i) Setting example 1 (Bus-bar VT=three phases, Line VT=phase-A)
507
(ii) Setting example 2 (Bus-bar VT=three phases, Line VT=phase-BC)
508
(iii) Setting example 3 (Bus-bar VT=Phase-C, Line VT= Three-phase)
509
2.35.5 VCHK1 and VCHK2 settings for 1.5CB system
510
2.35.6 Scheme and activation
512
2.35.7 Setting
514
2.35.8 Data ID
516
2.36 Transmission control function (DIF_COMM)
517
2.36.1 Data communication interface
518
(i) IEEE C37.94 (N=1)
518
(ii) IEEE C37.94 (N=3)
519
2.36.2 Synchronization control
519
(i) IEDs arrangement and setup
519
(i)-1 2Term mode
519
(i)-2 2Term-Dual mode
520
(i)-3 3Term mode
520
(ii) Time synchronization
521
(iii) Sampling address synchronization
523
(iv) Delay compensation
525
(v) Resynchronization
526
2.36.3 Topology of telecommunication
526
(i) Dual mode
526
(ii) Star mode
527
2.36.4 Communication setup
527
(i) Setting of Channel exchange
527
(ii) Setting in multiplexer
527
2.36.5 Setting
529
2.36.6 Data ID
530
2.37 Communication application (COMM_APPL)
531
2.37.1 Relay-address configuration
532
(i) Address configuration
532
(i)-1 ID numbering for two-terminals
532
(i)-2 Three-terminal application
532
2.37.2 Sub-communication channel for 1CB arrangement
533
(i) Normal (N=1) communication
533
(ii) Wide (N=3) communication
534
2.37.3 Sub-communication channel for 1.5CB arrangement
535
(i) Normal (N=1) communication
535
(ii) Wide (N=3) communication
536
2.37.4 Integral communication bits
536
2.37.5 Communication bits for OSTV
537
2.37.6 Usage of sub-communication channel
537
2.37.7 Setting of open terminal detection
537
2.37.8 Communication test
538
(i) Local test (Local-test)
538
(ii) Local loop test (Loop-test)
538
(iii) Open test (OPEN 1/OPEN 2)
538
2.37.9 Setting
539
2.37.10 Data ID
540
2.38 Protection common (PROT_COMMON)
557
2.38.1 Selection of breaker system
558
2.38.2 Decision of CB open/close status
558
(i) Signal option
558
(ii) Contact supervision
558
(iii) CB decision logic
559
2.38.3 Decision of DS open/close status
561
(i) Signal selection
561
(ii) Contact supervision
561
(iii) Logic
561
2.38.4 Dead line detection
562
(i) Under-voltage relay
562
(ii) Decision of CB operation
562
(iii) Detection time
562
(iv) Dead line detection logic
562
2.38.5 Detection of current change (OCD)
563
(i) Current change detection relay
563
(ii) OCD logic
563
2.38.6 User logic switches
564
2.38.7 Setting
565
2.38.8 Data ID
566
2.39 Cold load protection (CLP)
569
2.39.1 Scheme logic
570
2.39.2 Setting
572
2.39.3 Data ID
573
3 General control function
574
3.1 Control scheme
575
(i) Command reception in SBO mode
576
(i)-1 Reception of “select command”
576
(i)-2 Reception of “cancel command”
576
(i)-3 Reception of “operate command”
577
(ii) Command reception in DIR mode
577
3.2 Control mode
578
3.2.1 Select-before-operation mode (SBO)
578
(i) SBO with enhanced security (SBOes)
578
(ii) SBO with normal security (SBOns)
578
3.2.2 Direct-operation mode (DIR)
579
(i) DIR with enhanced security (DOes)
579
(ii) DIR with normal security (DOns)
579
3.3 Control hierarchy
581
3.3.1 Control level and control point
582
3.3.2 Selector switches and bay operations
582
(i) LCD operation
582
(ii) RCC, EWS, or OWS operation
582
3.3.3 Programming of control-right distributions
582
3.4 Common controls (CMNCTRL)
584
3.4.1 Double command blocking (DCB)
585
3.4.2 PLC_BIT/UNIT/BOOL signal
587
3.4.3 Provision of selected status
587
3.4.4 Miscellaneous settings
587
3.4.5 Setting
588
3.4.6 Signal
590
3.5 Local, remote and PLC control
594
3.5.1 Local control
595
3.5.2 Remote control
595
3.5.3 Programmable logic control (PLC)
595
3.5.4 Signal for Local/Remote control
596
3.5.5 Signal
597
3.6 LED reset function (LEDR)
598
3.6.1 Select logic for resetting LEDs
599
(i) Input signal required mapping
599
(ii) Output signal required mapping
600
(iii) Select condition
600
3.6.2 Cancel logic in SBO mode
602
(i) Receiving “Cancel” from the remote-end
602
(ii) Input signal required mapping
602
3.6.3 Operate logic for SBO/DIR mode
603
(i) Mapping required Input signal
603
(ii) Output signal required mapping
603
(iii) Operate condition
604
3.6.4 Settings in LED logics
605
(i) Settings using GR-TIEMS
605
(ii) Settings using IED screen
605
3.6.5 Mapping for IEC61850 communication
606
(i) Editing Logical Node
606
(i)-1 Defining SBO mode
606
(i)-2 Defining DIR mode
607
(ii) Mapping output data
607
(iii) Mapping input data
608
3.6.6 Setting
610
3.6.7 Signal
611
3.7 Counter function for the general (GCNT)
612
3.7.1 Counter setting for a signal
613
(i) Setting for count timing
613
(ii) Setting the maximum value
613
(iii) Setting the initial-value
614
(iv) Setting for the report (Dead band)
614
3.7.2 Select logics for SBO/DIR modes
615
(i) Receiving “Select command Reset” from the remote-end
615
(i)-1 Input point required mapping
615
(i)-2 Output signal to BO
615
(ii) Select condition
617
(iii) Signal name and number
618
(iv) Setting names
619
3.7.3 Cancel logic for SBO mode
620
(i) Receiving “Cancel” from the remote-end
620
(i)-1 Input point required mapping
620
(i)-2 Output signal to BO
620
(ii) Signal name and number
621
3.7.4 Operate logic for SBO/DIR modes
622
(i) Receiving “Operate command Reset” from the remote-end
622
(i)-1 Mapping required for Input point
622
(i)-2 Output signal to BO
622
(ii) Receiving “Operate command Reset” from the local-end
622
(ii)-1 New counter value
623
(ii)-2 Output signal to BO
623
(iii) Select condition
624
(iv) Signal names and number
624
3.7.5 Mapping for IEC61850 communication
625
(i) Editing Logical Node
625
(i)-1 Defining SBO mode
626
(i)-2 Defining DIR mode
626
(ii) Mapping output data
627
(iii) Mapping input data
627
3.7.6 Setting
629
3.7.7 Signal
630
3.8 Mode control function (MDCTRL)
632
3.8.1 Function
633
(i) Mode sensor
633
(ii) Interface for IEC61850
633
(iii) Input signal from control hierarchy
633
3.8.2 Mapping for IEC61850 communication
634
(i) Editing Logical Node
634
(i)-1 Defining SBO mode
634
(i)-2 Defining DIR mode
635
(ii) Mapping output data
635
(iii) Mapping input data
636
3.8.3 Setting
638
3.8.4 Signal
639
4 Control and monitoring application
641
4.1 Single position device function (SPOS)
642
4.1.1 Selection logic for SBO/DIR modes
643
(i) Receiving “select command ON” from the remote-end
643
(i)-1 Input point required mapping
643
(i)-2 Output signal to BO
644
(ii) Receiving “select command Off” from the remote-end
645
(ii)-1 Input point required mapping
645
(ii)-2 Output signal to BO
646
(iii) Receiving “Selection command On” from the local-end
646
(iii)-1 Input signal generated at the local-end.
646
(iii)-2 Output signal to BO
647
(iv) Receiving “Select command Off” from the local-end
648
(iv)-1 Input signal generated at the local-end.
648
(iv)-2 Output signal to BO
649
(v) Receiving “Selection command for ON” by PLC function
649
(v)-1 Input signal required from the PLC function.
649
(v)-2 Output signal to BO
650
(vi) Receiving “Select command Off” by PLC function
651
(vi)-1 Input signal from the PLC function
651
(vi)-2 Output signal to BO
652
(vii) Select condition
652
(vii)-1 How to add another select condition signal
652
(vii)-2 How to replace the original logic
653
(viii) Signal name and number
654
(ix) Setting names
657
4.1.2 Cancel logic for SBO mode
658
(i) Receiving “Cancel” from the remote-end
658
(i)-1 Input point required mapping
658
(i)-2 Output signal to BO
658
(ii) Receiving “Cancel” from the local-end
659
(ii)-1 Input signal generated at the local-end
659
(ii)-2 Output signal to BO
659
(iii) Cancel condition logic
660
(iv) Signal name and number
660
(v) Setting name
661
4.1.3 Operate logic for SBO/DIR modes
662
(i) Receiving “operate command On” from the remote- end
662
(i)-1 Mapping required for Input point
662
(i)-2 Output signal to BO
664
(ii) Receiving “operate command Off” from the remote end
665
(ii)-1 Mapping required for Input point from communication
665
(ii)-2 Output signal to BO
666
(iii) Receiving “operate command On” from the local-end
666
(iii)-1 Input signal generated at the local-end.
667
(iii)-2 Output signal to BO
668
(iv) Receiving “operate command Off” from the local-end
669
(iv)-1 Input signal generated at the local-end.
669
(iv)-2 Output signal to BO
671
(v) Receiving “operate command On” using the PLC function
671
(vi) Receiving “operate command Off” using PLC logic
672
(vii) Operate condition
672
(vii)-1 Adding another operate condition signal
672
(vii)-2 Replacing the original logic
673
(viii) Signal name and number
674
(ix) Setting names
676
4.1.4 Setup for BIO module
677
(i) BI connection for status-signals
677
(i)-1 Connection with Binary input circuit
677
(i)-2 Event suppression
678
(ii) BO connection for “Select command On/Off”
678
(iii) BO connection for “operate command On/Off”
679
(iv) Contact health check
680
(iv)-1 Setting for “Select command On/Off”
680
(iv)-2 Setting for “Operate Command On”
680
(iv)-3 Operate-Off command check
681
(iv)-4 Proper setting for the contact health check (normal setting, example #1)
681
(iv)-5 Setting for erroneous contact health check (improper setting, example #2)
681
(iv)-6 Setting for extra contact health check (special setting, example #3)
682
(v) Setting names
684
4.1.5 Mapping for IEC 61850 communication
685
(i) Editing Logical Node
685
(i)-1 Defining SBO mode
685
(i)-2 Defining DIR setting mode
686
(ii) Mapping output data
686
(iii) Mapping input data
687
4.1.6 Setting
689
4.1.7 Signal
690
4.2 Double position controller with synchronizing-checking (DPSY)
693
4.2.1 Select logic for SBO/DIR modes
694
(i) Receiving “select command Closing” from the remote-end
694
(i)-1 Input point required mapping
694
(i)-2 Output signal to BO
696
(ii) Receiving “select command Open” from the remote-end
697
(ii)-1 Input point required mapping
697
(ii)-2 Output signal to BO
698
(iii) Receiving “Select command Closing” from the local-end
698
(iii)-1 Input signal generated at the local-end
698
(iii)-2 Output signal to BO
699
(iv) Receiving “Select command Open” from the local-end
700
(iv)-1 Input signal generated at the local-end
700
(iv)-2 Output signal to BO
701
(v) Receiving “Select command Closing” by PLC function
701
(v)-1 Input signal from the PLC function
701
(v)-2 Output signal to BO
702
(vi) Receiving “Select command Open” by PLC function
703
(vi)-1 Input signal from the PLC function
703
(vi)-2 Output signal to BO
703
(vii) Select condition
704
(vii)-1 How to replace the original logic
704
(vii)-2 How to add another select condition signal
704
(viii) Signal name and number
706
(ix) Setting names
708
4.2.2 Cancel logic for SBO mode
709
(i) Receiving “Cancel” from the remote-end
709
(i)-1 Input point required mapping
709
(i)-2 Output signal to BO
710
(ii) Receiving “Cancel” from the local-end
710
(ii)-1 Input signal generated at the local-end
710
(ii)-2 Output signal to BO
711
(iii) Cancel condition logic
711
(iv) Signal name and number
711
(v) Setting name
712
4.2.3 Operate logic for SBO/DIR modes
713
(i) Receiving “operate command Closing” from the remote-end
713
(i)-1 Mapping required for Input point
713
(i)-2 Output signal to BO
715
(ii) Receiving “operate command Open” from the remote-end
715
(ii)-1 Mapping required for Input point from communication
715
(ii)-2 Output signal to BO
717
(iii) Receiving “operate command Closing” from the local-end
717
(iii)-1 Input signal generated at the local-end
717
(iii)-2 Output signal to BO
719
(iv) Receiving “operate command Open” from front panel
719
(iv)-1 Input signal generated at the local-end
719
(iv)-2 Output signal to BO
721
(v) Receiving “operate command Closing” using the PLC logic
721
(v)-1 Input signal from the PLC function
721
(v)-2 Output signal to BO
723
(vi) Receiving “operate command Open” using PLC logic
723
(vi)-1 Input signal from the PLC function
723
(vi)-2 Output signal to BO
725
(vii) Operate condition
725
(vii)-1 Replacing the original logic
725
(vii)-2 Adding another operate condition signal
725
(viii) Signal name and number
727
(ix) Setting names
728
4.2.4 Operation counter
729
(i) Receiving “change value for counter” from the remote end
730
(i)-1 Mapping of Input point required
730
(i)-2 Output signal to BO
730
(ii) Receiving “change value for counter” from the local-end
730
(ii)-1 Input signal from the front panel
730
(ii)-2 Output signal to BO
730
(iii) Operate condition for the counter
731
(iv) Signal names and number
732
(v) Setting name
732
4.2.5 Measurement of operation intervals
733
(i) Signal names and numbers
734
(ii) Setting names
734
4.2.6 Setup for BIO module
735
(i) BI connection for status signals
735
(i)-1 Grouping three-phase signals corresponding to a state
735
(i)-2 Acquisition of a signal corresponding to a phase
736
(i)-3 Event suppression
737
(ii) BO connection for “select command Open/Closing”
738
(iii) BO connection for “operate command Open/Closing”
738
(iv) Contact health check
739
(iv)-1 Setting for “Select command Closing”
740
(iv)-2 Setting the “Select command Open”
740
(iv)-3 Setting for “Operate command Closing”
740
(iv)-4 Setting for “Operate command Open”
741
(iv)-5 Setting for the contact health check (normal setting, example)
742
(iv)-6 Settings for erroneous contact health check (improper setting, example #2)
743
(iv)-7 Settings for extra contact health check (special setting, example #3)
744
(v) Setting names
745
4.2.7 Mapping for IEC 61850 communication
746
(i) Editing Logical Node
746
(i)-1 Defining SBO mode
746
(i)-2 Defining DIR mode
747
(ii) Mapping output data
747
(iii) Mapping input data
748
4.2.8 Setting
750
4.2.9 Signal
752
4.3 Software switch controller function (SOFTSW)
757
4.3.1 SOFTSW controlling
758
(i) Command blocking (CBK)
758
(ii) Interlock bypassing (ICB) provided
759
(iii) Synchronism bypassing (SCB)
759
(iv) S43-01 to S43-61 controlling provided by SOFTSW1 to SOFTSW61†
759
(v) SOFTSW output-status
760
4.3.2 Control logics for SBO/DIR modes
761
(i) Receiving “select command for On operation” from the remote-end
761
(i)-1 Input point required mapping
761
(i)-2 Output signal for monitoring
762
(ii) Receiving “select command for Off operation” from the remote end
762
(ii)-1 Input point required mapping
762
(ii)-2 Output signal for monitoring
762
(iii) Receiving “Selection command for On operation” from the front panel
762
(iii)-1 Input signal
763
(iii)-2 Output signal for monitoring
763
(iv) Receiving “Select command for Off operation” from the front panel
763
(iv)-1 Input signal
763
(iv)-2 Output signal for monitoring
764
(v) Receiving “Select command for On operation” using the PLC function
764
(v)-1 Input signal required to connect
764
(v)-2 Output signal for monitoring
765
(vi) Receiving “Select command for Off operation” using PLC function
765
(vi)-1 Input signal required to connect
765
(vi)-2 Output signal to monitoring
766
(vii) Select condition
766
(viii) Signal name and number
767
(ix) Setting names
769
4.3.3 Cancel logic for SBO mode
770
(i) Receiving “Cancel” from remote-end
770
(ii) Receiving “Cancel” from local-end
770
4.3.4 Operate logic for SBO/DIR modes
770
(i) Receiving “operate command On” from remote-end
771
(ii) Receiving “operate command Off” from remote-end
771
(iii) Receiving “operate command On” from the local end
772
(iv) Receiving “operate command Off” from the local end
772
(v) Receiving “operate command On” using PLC logic
773
(vi) Receiving “operate command Off” using PLC logic
773
(vii) Operate condition
774
(viii) Signal name and number
775
4.3.5 Mapping for IEC 61850 communication
778
(i) Editing Logical Node
778
(i)-1 Defining SBO mode
778
(i)-2 Defining DIR mode
779
(ii) Mapping output data
779
(iii) Mapping input data
780
4.3.6 Setting
782
4.3.7 Signal
783
4.4 Operation time reset function (OPTIM)
792
4.4.1 Select logic for SBO/DIR modes
794
(i) Input point required mapping
794
(ii) Output signal required to map
795
(iii) Select condition
795
4.4.2 Cancel logic in SBO mode
797
(i) Receiving “Cancel” from the remote-end
797
(ii) Input point required mapping
797
4.4.3 Operate logic for SBO/DIR modes
798
(i) Input signal required mapping
798
(ii) Output signal required to map
798
(iii) Operate condition
799
4.4.4 Mapping for IEC61850 communication
800
(i) Editing Logical Node
800
(i)-1 Defining SBO mode
801
(i)-2 Defining DIR mode
801
(ii) Mapping output data
802
(iii) Mapping input data
802
4.4.5 Setting
804
4.4.6 Signal
805
4.5 Total time measurement function (TOTALTIM)
806
4.5.1 Operation feature
807
(i) Time accumulation process
807
(ii) Acquisition of operation signal
807
(iii) Setting for the report (Dead band)
808
(iv) Data correction
808
4.5.2 Preparation for operation
809
4.5.3 Mapping for IEC 61850 communication
810
(i) Editing Logical Node
810
(i)-1 Defining SBO mode
810
(i)-2 Defining DIR mode
811
(ii) Mapping output data
811
(iii) Mapping input data
812
4.5.4 Setting
814
4.5.5 Signal
815
4.6 Synchronizing check for different network (SYNDIF)
819
4.6.1 Relays to check line-outage
820
(i) Overvoltage-relay elements (OVr1, OVi1)
820
(ii) Undervoltage-relay elements (UVr1, UVi1)
821
4.6.2 Synchronization check relays
822
(i) Synchronism-relays (SyncRy1-dV, SyncRy1-df, SyncRy1-dθ)
823
(i)-1 Voltage-variance (ΔV) (see Figure 4.6-3)
823
(i)-2 Phase-angle variance (Δθ) (see Figure 4.6-4)
824
(i)-3 Frequency-variance (Δf)
824
(i)-4 Notice and tips
824
(ii) Split-synchronism-check element (SyncRy1-θ=0, SyncRy1-θless)
826
(ii)-1 Calculation of synchronization point
826
(ii)-2 Check for slip cycle
826
(ii)-3 Advance time
826
4.6.3 Line-outage check
828
(i) Voltage conditions
828
(ii) Check logic and settings
829
(ii)-1 Permission signal “SYNC01_SLD_VCS”†
832
(ii)-2 Permission signal “SYNC01_SYN_CLC”‡
832
(iii) Adding other voltage-conditions using PLC signals
832
(iv) Relay selection using PLC signals
832
4.6.4 Synchronization check
833
(i) Synchronization conditions
833
(ii) Check logic and settings for synchronous network
835
(iii) Check logic and settings for asynchronous network
835
(iv) Bypassing synchronization check
835
(v) Unsuccessful synchronization check
836
(vi) Adding other sync-conditions using PLC signals
836
(vii) Relay selection using PLC signals
836
(viii) Synchronization logic test
836
4.6.5 Relay selection for checking synchronization
837
4.6.6 Voltage selection for line arrangement
839
(i) Setting example
839
4.6.7 Setting
841
4.6.8 Signal
843
4.7 Software interlock function (ILK)
846
4.7.1 ILK specification
847
(i) Maximum number of interlock-checks
847
(ii) GOOSE receiving information
847
4.7.2 Interlock-check formula
848
4.7.3 Interlock-check method
850
(i) Node and input/output signals
850
(ii) Nodes and formulae for interlock-check
851
(iii) Purpose of Quality information in the output signal
852
(iii)-1 AND interlock operator
852
(iii)-2 OR interlock operator
853
(iii)-3 NOR interlock operator
854
(iii)-4 COMP interlock operator
855
(iii)-5 Device status output by control functions transposed
855
4.7.4 Configuration of Interlock formulae
856
4.7.5 Signal
857
4.8 Double position device function (DPOS)
864
4.8.1 Select logic for SBO/DIR modes
865
(i) Receiving “Select command On” from the remote-end
865
(i)-1 Input point required mapping
865
(i)-2 Output signal to BO
865
(ii) Receiving “Select command Off” from the remote-end
867
(ii)-1 Input point mapped from the communication
867
(ii)-2 Output signal to BO
867
(iii) Receiving “Select command On” from the local-end
869
(iii)-1 Input signal generated at the local-end
869
(iii)-2 Output signal to BO
869
(iv) Receiving “Select command Off” from the local-end
871
(iv)-1 Input signal generated at the local-end
871
(iv)-2 Output signal to BO
871
(v) Receiving “Select command On” by PLC function
873
(v)-1 Input signal from the PLC function
873
(v)-2 Output signal to BO
873
(vi) Receiving “Select command Off” by PLC function
875
(vi)-1 Input signal from the PLC function
875
(vi)-2 Output signal to BO
875
(vii) Select condition
877
(vii)-1 How to replace the original logic
877
(vii)-2 How to add another select condition signal
877
(viii) Signal name and number
880
(ix) Setting names
882
4.8.2 Cancel logic for SBO mode
883
(i) Receiving “Cancel” from the remote-end
883
(i)-1 Input point required mapping
883
(i)-2 Output signal to BO
883
(ii) Receiving “Cancel” from the local-end
884
(ii)-1 Input signal generated at the local-end
884
(ii)-2 Output signal to BO
885
(iii) Cancel condition logic
885
(iv) Signal name and number
886
(v) Setting name
886
4.8.3 Operate logic for SBO/DIR modes
887
(i) Receiving “Operate command On” from the remote-end
887
(i)-1 Mapping required for Input point
887
(i)-2 Output signal to BO
887
(ii) Receiving “Operate command Off” from the remote-end
889
(ii)-1 Mapping required for Input point
889
(ii)-2 Output signal to BO
889
(iii) Receiving “Operate command On” from the local-end
891
(iii)-1 Input signal generated at the local-end
891
(iii)-2 Output signal to BO
891
(iv) Receiving “Operate command Off” from the local-end
893
(iv)-1 Input signal generated at the local-end
893
(iv)-2 Output signal to BO
893
(v) Receiving “Operate command On” using the PLC function
895
(v)-1 Input signal from the PLC function
895
(v)-2 Output signal to BO
895
(vi) Receiving “Operate command Off” using PLC function
897
(vi)-1 Input signal from the PLC function
897
(vi)-2 Output signal to BO
897
(vii) Operate condition
899
(vii)-1 Replacing the original logic
899
(vii)-2 Adding another operate condition signal
899
(viii) Signal name and number
901
(ix) Setting names
903
4.8.4 Operation counter
904
(i) Receiving “change value for counter” from the remote-end
905
(i)-1 Mapping of Input signal required
905
(i)-2 Output signal to BO
905
(ii) Receiving “change value for counter” from the local-end
905
(ii)-1 Input signal from the front panel
905
(ii)-2 Output signal to BO
905
(iii) Operate condition for the counter
906
(iv) Signal names and number
906
(v) Setting name
907
4.8.5 Measurement of operation intervals
908
(i) Signal names and numbers
909
(ii) Setting name
909
4.8.6 Setup for BIO module
910
(i) BI connection for status signals
910
(i)-1 Grouping three-phase signals corresponding to a state
910
(i)-2 Acquisition of a signal corresponding to a phase
911
(i)-3 Event suppression
912
(ii) BO connection for “Select command On/Off”
913
(iii) BO connection for “Operate command On/Off”
914
(iv) Contact health check
914
(iv)-1 Setting for “Select command On”
915
(iv)-2 Setting for “Select command Off”
915
(iv)-3 Setting for “Operate command On”
916
(iv)-4 Setting for “Operate command Off”
916
(iv)-5 Setting for the contact health check (normal setting, example #1)
917
(iv)-6 Settings for erroneous contact health check (improper setting, example #2)
918
(iv)-7 Settings for extra contact health check (special setting, example #3)
919
(v) Signal name and number
920
(vi) Setting names
920
4.8.7 Mapping for IEC61850 communication
921
(i) Editing Logical Node
921
(i)-1 Defining SBO mode
922
(i)-2 Defining DIR mode
922
(ii) Mapping output data
923
(iii) Mapping input data
923
4.8.8 Setting
925
4.8.9 Signal
927
4.9 Three position device function (TPOS)
930
4.9.1 Select logic for SBO/DIR modes
932
(i) Receiving “select command P1-control” from the remote-end
932
(i)-1 Input point required mapping
932
(i)-2 Output signal to BO
933
(ii) Receiving “select command P2-control” from the remote-end
934
(ii)-1 Input point mapped from the communication
934
(ii)-2 Output signal to BO
935
(iii) Receiving “select command P3-control” from the remote-end
935
(iii)-1 Input point mapped from the communication.
935
(iii)-2 Output signal to BO
936
(iv) Receiving “Select command P1-control” from the local-end.
937
(iv)-1 Input signal generated at the local-end
937
(iv)-2 Output signal to BO
938
(v) Receiving “Select command P2-control” from the local-end.
938
(v)-1 Input signal generated at the local-end
939
(v)-2 Output signal to BO
940
(vi) Receiving “Select command P3-control” from the local-end
940
(vi)-1 Input signal generated at the local-end
940
(vi)-2 Output signal to BO
941
(vii) Receiving “Select command P1-control” by PLC function
941
(vii)-1 Input signal from the PLC function
942
(vii)-2 Output signal to BO
943
(viii) Receiving “Select command P2-control” by PLC function
943
(viii)-1 Input signal from the PLC function
944
(viii)-2 Output signal to BO
945
(ix) Receiving “Select command P3-control” by the PLC function
945
(ix)-1 Input signal from the PLC function
946
(ix)-2 Output signal to BO
947
(x) Select condition
947
(x)-1 How to replace the original logic
947
(x)-2 How to add another select condition signal
948
(xi) Signal name and number
950
(xii) Setting names
952
4.9.2 Cancel logic for SBO mode
953
(i) Receiving “Cancel” from the remote-end
953
(i)-1 Input point required mapping
953
(i)-2 Output signal to BO
953
(ii) Receiving “Cancel” from the local-end
954
(ii)-1 Input signal
954
(ii)-2 Output signal to BO
954
(iii) Cancel condition logic
955
(iv) Signal name and number
955
(v) Setting name
956
4.9.3 Operate logic for SBO/DIR modes
957
(i) Receiving “Operate command for P1-control” from the remote-end
957
(i)-1 Mapping required for Input point
957
(i)-2 Output signal to BO
959
(ii) Receiving “Operate command P2-control” from the remote-end
959
(ii)-1 Input signal required mapping
959
(ii)-2 Output signal to BO
961
(iii) Receiving “Operate command P3-control” from the remote-end
961
(iii)-1 Input signal required mapping
961
(iii)-2 Output signal to BO
963
(iv) Receiving “Operate command P1-control” from the local-end
963
(iv)-1 Input signal generated at the local-end
963
(iv)-2 Output signal to BO
965
(v) Receiving “operate command P2-control” from the local-end
965
(v)-1 Input signal generated at the local-end.
965
(v)-2 Output signal to BO
967
(vi) Receiving “operate command P3-control” from the local-end
967
(vi)-1 Input signal generated at the local-end
967
(vi)-2 Output signal to BO
969
(vii) Receiving “operate command P1-control” using the PLC function
969
(vii)-1 Input signal from the PLC function
969
(vii)-2 Output signal to BO
971
(viii) Receiving “operate command P2-control” using the PLC function
971
(viii)-1 Input signal from the PLC function
971
(viii)-2 Output signal to BO
973
(ix) Receiving “operate command P3-control” using the PLC function
973
(ix)-1 Input signal required to connect
973
(ix)-2 Output signal to BO
975
(x) Operate condition
975
(x)-1 Replacing the original logic
975
(x)-2 Adding another operate condition signal
975
(xi) Signal name and number
977
(xii) Setting names
979
4.9.4 Operation counter
981
(i) Receiving “change value for counter” from the remote-end
982
(i)-1 Mapping of Input point required
982
(i)-2 Output signal to BO
982
(ii) Receiving “change value for counter” from the local-end
982
(ii)-1 Input signal from the front panel
982
(ii)-2 Output signal to BO
983
(iii) Operate condition for the counter
983
(iv) Signal names and number
983
(v) Setting name
984
4.9.5 Measurement of operation Intervals
985
(i) Signal names and numbers
987
(ii) Setting names
987
4.9.6 Setup for BIO module
988
(i) BI connection for status signals
988
(i)-1 Connection with Binary input circuits
988
(i)-2 Decision by input signals
989
(i)-3 Event suppression detector
990
(ii) BO connection for “select commands”
990
(iii) BO connection for “operate command”
991
(iv) Contact health check
992
(iv)-1 Setting for “select command P1/P2/P3”
992
(iv)-2 Setting for “Operate command P1/P2/P3”
993
(iv)-3 Proper setting for the contact health check (normal setting, example #1)
994
(iv)-4 Setting for erroneous in contact health check (improper setting, example #2)
995
(iv)-5 Setting for extra contact health check (special setting, example #3)
996
(v) Signal name and number
997
(vi) Setting names
998
4.9.7 Mapping for IEC61850 commination
999
(i) Editing Logical Node
999
(i)-1 Defining SBO mode
999
(i)-2 Defining DIR mode
1000
(ii) Mapping output data
1000
(iii) Mapping input data
1001
4.9.8 Setting
1003
4.9.9 Signal
1005
4.10 Event detection function for general BIs (GENBI)
1010
4.10.1 Operation features
1011
(i) Signal acquisition process
1011
(ii) Event suppression process
1011
4.10.2 Mapping for IEC61850 communication
1014
(i) Editing Logical Node
1014
(ii) Mapping output data
1014
4.10.3 Setting
1016
4.10.4 Signals
1017
4.11 Automatic sequence control function (ASEQ)
1019
4.11.1 Function setup
1020
4.11.2 Preparation of the operation
1021
4.11.3 Example of automatic sequence operation
1022
4.11.4 Control hierarchy conditions
1024
4.11.5 Input for emergency stop
1024
4.11.6 Mapping for IEC61850 communication
1026
(i) Editing Logical Node
1026
(i)-1 Defining SBO mode
1026
(i)-2 Defining DIR mode
1027
(ii) Mapping output data
1027
(iii) Mapping input data
1028
4.11.7 Setting
1030
4.11.8 Signal
1031
5 Technical Description
1033
5.1 IED case and module slot
1036
5.1.1 Type using compression terminals
1037
(i) 1/1 size case
1037
(i)-1 Viewing from the front side (Figure 5.1-2.a)
1037
(i)-2 Viewing from the rear side (Figure 5.1-2.b)
1037
(i)-3 Schematic figure (Figure 5.1-2.c)
1037
(ii) 3/4 size case
1039
(iii) 1/2 size case
1041
5.1.2 Type using ring terminals
1043
(i) 1/1 size case
1043
(i)-1 Viewing from the front side (Figure 5.1-2.a)
1043
(i)-2 Viewing from the rear side (Figure 5.1-2.b)
1043
(i)-3 Schematic figure (Figure 5.1-2.c)
1043
(ii) 3/4 size case
1045
(iii) 1/2 size case
1047
5.2 Transformer module for AC analog input (VCT)
1049
5.2.1 VCT11B
1050
5.2.2 VCT12B
1051
5.2.3 Constitution of VCT
1052
5.2.4 Setting VCT ratio
1053
(i) Setting a ratio for the VT
1053
(ii) Setting a ratio for the CT
1053
(iii) Setting list
1053
5.2.5 Changing VCT rated current
1054
(i) Rating jumpers
1054
(ii) DEP settings
1054
(iii) Example for VCT12B rated current change
1055
(iii)-1 VCT jumper: Close or open the circuits named W* numbers corresponding to the currents. The hatched areas are required to close or open.
1055
(iii)-2 Configuration switch: Change the CPU to the constrained mode (see Section Signal processing and communication module).
1056
(iii)-3 Writing settings: [AI1_Ch6/7/8/9/14_Rating] settings, corresponding to the CTs, shall have DEP absolutely. Rewriting the setting items is required with GR-TIEMS. Confirm that DEP has been set definitely after the rewrite (for more detail, see ...
1056
5.2.6 Settings for residual voltage, CT polarity, and busbar arrangements
1057
(i) Setting [APPL-Ves2] = Ve
1057
(ii) Setting [APPL-Ves2] = Vs2
1057
(iii) Setting [APPL-Ves2] = Off
1058
(iv) Setting [APPL-CTSELECT] = 1CT
1058
(v) Setting [APPL-CTSELECT] = 2CT
1059
(vi) CT polarity settings
1060
5.3 Signal processing and communication module (CPU)
1062
5.3.1 Signal processing
1062
5.3.2 Configuration switch
1063
5.3.3 Communication modules
1064
5.3.4 Location of communication modules
1068
5.4 Binary IO module (BI, BO, and BIO)
1071
5.4.1 Binary input feature
1072
5.4.2 Binary input circuit
1073
(i) Setting threshold level
1077
(i)-1 For Standard type (the BI1A module and others)
1077
(i)-2 For Variable type (exclusive for the BI2A)
1079
(ii) Comparison feature for contact chatter
1081
(iii) CPL switch
1082
(iv) Delayed pick-up and delayed drop-off signal
1082
(v) Logic level inversion
1082
(vi) How to set the settings for binary input circuits
1082
5.4.3 Binary output feature
1084
5.4.4 Binary output circuit
1086
(i) CPL switch
1088
(ii) Selection of input signals
1088
(iii) Logic gate switch
1088
(iv) Delayed pick-up/delayed drop-off signal
1088
(v) Logic level inversion
1089
(vi) Logic timer switch
1089
(vi)-1 Instant type
1089
(vi)-2 Delay type
1089
(vi)-3 Dwell type
1089
(vi)-4 Latch type
1089
(vii) How to set the settings for binary output circuits
1090
(viii) PLC and the binary output circuits
1091
5.4.5 Structure of binary IO Module
1091
5.4.6 Settings of binary input circuits
1097
(i) Setting table (IO_SLOT1) at IO#1 (Function ID: 200B01)
1097
(i)-1 For the standard type being furnished
1097
(i)-2 For the variable type being furnished
1097
(ii) Setting tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n (Function ID: 200B02 to 200B0n)
1098
(ii)-1 For the standard type being furnished
1098
(ii)-2 For the variable type being furnished
1098
5.4.7 Signals (Data ID) of binary input circuits
1099
(i) Table (IO_SLOT1) at IO#1 (Function ID: 200B01)
1099
(i)-1 Before the filer
1099
(i)-2 After the filter
1099
(i)-3 The ends of binary input circuits
1100
(ii) Tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n (Function ID: 200B02 to 200B0n)
1101
(ii)-1 Before the filter
1101
(ii)-2 After the filter
1101
(ii)-3 The ends of binary input circuits
1101
5.4.8 Settings of binary output circuits
1102
(i) Setting table (IO_SLOT1) at IO#1 (Function ID 200B01)
1102
(ii) Setting tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n (Function ID 200B02 to 200B0n)
1103
5.4.9 Signals (Data ID) of binary output circuits
1104
(i) Table (IO_SLOT1) at IO#1 (Function ID: 200B01)
1104
(i)-1 Before the contact-driver
1104
(i)-2 After the contact-driver
1104
(i)-3 Connection points for the PLC
1105
(ii) Tables (IO_SLOT2 to SLOTn) at IO#2 to IO#n (Function ID: 200B02 to 200B0n)
1105
(ii)-1 Before the contact-driver
1105
(ii)-2 After the contact-driver
1105
(ii)-3 Connection points for the PLC
1105
5.5 Power supply module (PWS)
1106
5.5.1 PWS structure
1106
5.5.2 Input and output items of PWS
1108
5.5.3 DC voltage monitoring
1109
(i) Threshold voltage for detection/non-detection of power error
1109
(ii) Recommended setting for the voltage level
1110
5.6 Human Machine Interface (HMI)
1111
5.6.1 Outlook
1111
5.6.2 LED Indicators
1112
(i) Selection of input signals
1112
(ii) Logic gate switch
1112
(iii) Delayed pick-up/delayed drop-off signal
1113
(iv) Logic level inversion
1113
(v) Logic timer switch
1114
(v)-1 Instant type
1114
(v)-2 Delay type
1114
(v)-3 Dwell type
1114
(v)-4 Latch type
1114
(vi) Selection of the LED color
1114
5.6.3 Function keys with LEDs
1117
(i) Screen jump pressing the function key
1117
(ii) Binary signal generated pressing the function key
1117
(iii) Lighting LEDs on F1 to F7
1118
5.6.4 Monitoring jacks
1122
5.6.5 Operation keys
1124
(i) L/R key
1124
(ii) Operation keys except L/R key
1124
5.7 Clock function
1125
5.7.1 Clock setting
1125
5.7.2 Selection of date and time formats
1125
5.7.3 Time Synchronization
1126
(i) Synchronization using SNTP
1126
(i)-1 Example of SNTP synchronization
1126
(i)-2 Setting procedure
1126
(ii) Synchronization using IRIG-B
1127
(ii)-1 Example of IRIG-B synchronization
1127
(ii)-2 Setting procedure
1127
(ii)-3 Setting year in IRIG-B
1127
(ii)-4 Setting UTC/local time
1127
(iii) Synchronization using BI signal
1128
(iii)-1 Example of time synchronization via BI circuit
1128
(iii)-2 Setting procedure
1129
5.7.4 Setting time zone
1130
5.7.5 DST setting (Summer time setting)
1131
(i) DST set by the day (Mon to Sun) of week
1131
(ii) DST set by the day (1st or 15th) of month
1131
(iii) Time shift
1132
5.7.6 Setting
1133
5.8 Group setting for protection functions
1134
(i) Changing group number by menu operation
1134
(ii) Changing group number by user-programming
1134
(iii) Setting
1136
(iv) Signal (Data ID)
1136
6 Engineering tool
1137
6.1 Overview of GR-TIEMS
1138
6.2 Connection
1139
6.3 Common tools
1140
(i) Project management
1140
(ii) Comparison
1140
(iii) Pocket label creator
1140
(iv) Logging
1140
(v) Double command block
1140
6.4 Monitoring tools
1140
6.5 Record tools
1141
(i) Fault record
1141
(ii) Disturbance record
1141
(iii) Event list
1141
6.6 Generic configuration tools
1141
(i) Setting (general setting for the relay and controlling functions)
1141
(ii) Setting I/O
1141
(iii) Setting event list
1142
(iv) Interlock configurator
1142
6.7 IEC 61850 configuration tool
1142
6.8 IEC 60870-5-103 configuration tool
1142
6.9 MIMIC configuration tool
1142
7 PLC function
1143
7.1 Overview of PLC function
1144
7.2 PLC data error
1144
7.3 PLC driver
1145
7.3.1 Monitoring point for PLC driver
1145
(i) BIT type
1145
(ii) USINT type
1147
(iii) UINT type
1147
(iv) UDINT type
1148
(v) SINT type
1148
(vi) INT type
1148
(vii) DINT type
1148
7.4 PLC setting samples
1149
7.4.1 Tele-protection scheme using DISCAR and DEFCAR commands
1149
(i) Transmitter tele-protection logic
1149
(ii) Receiver tele-protection logic
1152
(iii) PLC program
1154
7.4.2 Transfer trip using DTT scheme
1155
(i) Transmitter and receiver schemes
1155
(i)-1 Terminal J
1155
(i)-2 Terminal G
1156
(ii) Sample DTT logics
1158
7.4.3 Remote DIFL/DIFGL trip using communication scheme
1159
(i) Transmitter and receiver schemes
1159
(ii) Sample local and remote logics
1163
7.5 Timer variable settings using PLC drivers
1164
Example of timer action1
1165
Example of timer action2
1165
(i) Setting value
1166
8 Recording function
1169
8.1 Fault recorder
1170
8.1.1 Types of recording information
1170
(i) Date and time at fault
1170
(ii) Tripped phase information
1170
(iii) Mode information
1170
(iv) FL calculation result
1171
(v) Evolving faults
1171
(vi) Fault quantities and pre-fault-quantities
1171
8.1.2 Screen information
1173
8.1.3 Setup for the fault recorder
1174
(i) Operation identifiers (ID1–ID128)
1174
(ii) Logical signals (ID201–ID264)
1174
(iii) Additional triggers for the recording
1175
(iv) Time setting for Pre-fault
1175
(v) Unit setting for the quantities
1175
8.1.4 Scheme logic
1177
8.1.5 Setting
1178
8.1.6 Signal (Data ID)
1178
8.2 Event recorder
1179
8.2.1 Trigger signals
1179
8.2.2 Trigger modes
1184
(i) ‘On’ mode
1184
(ii) ‘Off’ mode
1184
(iii) ‘On-Off’ mode
1184
(iv) ‘Change’ mode
1184
8.2.3 Screen information
1185
8.2.4 Setup for the event recorder
1185
8.2.5 Setting
1186
8.2.6 Signal (Data ID)
1186
8.3 Disturbance recorder
1187
8.3.1 Recording time and amount
1187
(i) Time settings
1187
(ii) Sampling rate setting
1187
(iii) Trip command setting
1187
8.3.2 Relays within disturbance recorder
1187
(i) OC-DRT relay setting
1188
(ii) EF-DRT relay setting
1188
(iii) UV-DRT relay setting
1188
(iv) UVS-DRT relay setting
1188
8.3.3 Maximum number for recording disturbance phenomena
1188
8.3.4 Number of analog quantities and logical signals for disturbance recorder
1188
(i) Number of analog quantities
1188
(ii) Number of logical signals
1189
8.3.5 Trigger settings for PLC programming
1191
8.3.6 Screen information
1191
8.3.7 Interpolation of transferred data
1192
8.3.8 Setting
1193
8.3.9 Signal (Data ID)
1194
8.4 Transferred information during fault
1195
8.4.1 Transferred metering values
1196
8.4.2 Transferred information about tripped phase and mode
1198
8.4.3 Transferred state information
1198
8.4.4 Transferring record value and information
1199
9 Monitoring function
1210
9.1 Outline
1211
9.2 Metering data (Metering group)
1211
9.2.1 Metering information on the screen
1212
9.2.2 Setting for measurements
1213
(i) Selecting either primary/secondary values
1213
(ii) Unit setting
1213
9.2.3 Diminishing a very small value to display zero
1214
9.2.4 Flow settings for active/reactive/apparent powers
1214
(i) Metering in active power (P)
1214
(ii) Metering in reactive power (Q)
1215
9.2.5 Polarity setting for power factor values
1215
(i) AP setting
1215
(ii) AP+PR setting
1216
9.2.6 Setting for the report (Dead band feature)
1217
(i) Counting operation in SD feature
1217
(ii) Check cycle in SD feature
1217
(iii) Setting bands for the operation
1218
9.3 Statistics data (Power value group)
1219
9.3.1 Power information on the screen
1219
9.3.2 Setting for power values
1219
9.3.3 Regulation of power values
1219
9.4 Statistics data (Demand value group)
1220
9.4.1 Demand information on the screen
1220
9.4.2 Max/Min/Averaged information about the demand feature
1220
(i) Maximum and minimum value
1221
(ii) Averaged value
1221
9.4.3 Demand cycle
1221
9.4.4 Resetting data in demand features
1221
9.5 Statistics data (Peak-demand value group)
1222
9.5.1 Max/Min/Averaged information about the peak-demand feature
1222
(i) Maximum value
1222
(ii) Minimum value
1222
(iii) Averaged value
1222
9.5.2 Resetting data of peak-demand features
1222
9.6 Statistics data (Counter group)
1223
9.6.1 Count information on the screen
1223
9.6.2 Report setting for GCNT (Dead band feature)
1223
9.7 Statistics data (Accumulated time)
1224
9.8 Statistics data (Total time group)
1225
9.8.1 Time information on the screen
1225
9.8.2 Report setting for TOTALTIM (Dead band feature)
1225
9.9 Monitoring for miscellaneous functions
1226
(i) Relay element
1226
(ii) Communication
1226
(iii) Binary IO
1226
(iv) Goose monitoring
1226
(v) Diagnostics
1226
9.10 Setting
1227
9.11 Signal and measurand (Data ID)
1228
(i) Common signal
1228
(ii) Measurand in Soft 33 and VCT11B operating with 1 remote terminal
1229
(iii) Measurand in Soft 33 and VCT11B operating with 2 remote terminals
1233
(iv) Measurand in Soft 33 and VCT12B operating with 1 remote terminal
1237
(v) Measurand in Soft 33 and VCT12B operating with 2 remote terminals
1241
(vi) Measurand in Soft 37 and VCT11B operating with 1 remote terminal
1245
(vii) Measurand in Soft 37 and VCT11B operating with 2 remote terminals
1249
10 Automatic supervision
1253
10.1 Outline of automatic supervision
1254
(i) Error levels
1254
(ii) Error LED and LCD error message
1255
(iii) Error outputs with contacts and binary output circuits
1256
(iii)-1 Error output by PWS contact†
1256
(iii)-2 Locking out of BO circuit operation‡
1256
(iv) Affection of application operation by error levels
1256
10.2 Generic supervision tasks
1257
10.2.1 Mismatch between ROM and RAM data (ROM/RAM error)
1259
(i) Error level
1259
(ii) Error message
1259
10.2.2 Supervision of check-sum error (SUM error)
1260
(i) Error level
1260
(ii) Error message
1260
10.2.3 Supervision of RAM (RAM error)
1261
(i) Error level
1261
(ii) Error message
1261
10.2.4 Supervision of ECC on memory (ECC error)
1262
(i) Error level
1262
(ii) Error message
1262
10.2.5 Supervision of MRAM (MRAM)
1263
(i) Error level
1263
(ii) Error message
1263
10.2.6 Supervision of FPGA (FPGA error)
1264
(i) Error level
1264
(ii) Error message
1264
10.2.7 Supervision of program codes (CPU error)
1265
(i) Error level
1265
(ii) Error message
1265
10.2.8 Supervision of task operation (RUN error)
1266
(i) Error level
1266
(ii) Error message
1266
10.2.9 Detecting non-maskable interrupt (NMI error)
1267
(i) Error level
1267
(ii) Error message
1267
10.2.10 Supervision of sampling period (SMP error)
1268
(i) Error level
1268
(ii) Error message
1268
10.2.11 Supervision of setting data (Setting error)
1269
(i) Error level
1269
(ii) Error message
1269
10.2.12 Supervision of real-time clock (RTC error)
1270
(i) Error level
1270
(ii) Error message
1270
10.2.13 Supervision of analog input data on VCTs (AI ACC error)
1271
(i) Error level
1271
(ii) Error message
1271
10.2.14 Abnormal currents flowing in CTs (CT error)
1272
(i) Error level
1272
(ii) Error message
1272
10.2.15 Current transformer failure (CT fail)
1273
(i) Error level
1273
(ii) Error message
1273
10.2.16 Supervision of the current in zero-sequence (I0 error)
1274
(i) Error level
1274
(ii) Error message
1274
10.2.17 Supervision of voltage in negative-sequence (V2 error)
1275
(i) Error level
1275
(ii) Error message
1275
10.2.18 Supervision of voltage in zero-sequence (VZ error)
1276
(i) Error level
1276
(ii) Error message
1276
10.2.19 Supervision of binary IO module#1 (BIO#1 error)
1277
(i) Error level
1277
(ii) Error message
1277
10.2.20 Supervision of binary IO module#2 (BIO#2 error)
1278
(i) Error level
1278
(ii) Error message
1278
10.2.21 Supervision of binary IO module#3 (BIO#3 error)
1279
(i) Error level
1279
(ii) Error message
1279
10.2.22 Supervision of binary IO module#4 (BIO#4 error)
1280
(i) Error level
1280
(ii) Error message
1280
10.2.23 Supervision of binary IO module#5 (BIO#5 error)
1281
(i) Error level
1281
(ii) Error message
1281
10.2.24 Supervision of binary IO module#6 (BIO#6 error)
1282
(i) Error level
1282
(ii) Error message
1282
10.2.25 Supervision of binary IO module#7 (BIO#7 error)
1283
(i) Error level
1283
(ii) Error message
1283
10.2.26 Supervision of binary IO module#8 (BIO#8 error)
1284
(i) Error level
1284
(ii) Error message
1284
10.2.27 Supervision of human machine interface (HMI error)
1285
(i) Error level
1285
(ii) Error message
1285
10.2.28 Supervision of power supply module (Power error)
1286
(i) Error level
1286
(ii) Error message
1286
10.2.29 Supervision of data in PLC function (PLC data error)
1287
(i) Error level
1287
(ii) Error message
1287
10.2.30 Voltage transformer failure (VT fail)
1289
(i) Error level
1289
(ii) Error message
1289
10.2.31 Supervision of circuit breaker contacts (CB1/CB2 fail)
1290
(i) Error level
1290
(ii) Error message
1290
10.2.32 Supervision of disconnector contacts (DS fail)
1291
(i) Error level
1291
(ii) Error message
1291
10.2.33 Supervision of LAN status (LAN error)
1292
(i) Error level
1292
(ii) Error message
1292
10.2.34 Supervision of response for pinging (Ping error)
1293
(i) Error level
1293
(ii) Error message
1293
10.2.35 Supervision of link redundant entity (LRE error)
1294
(i) Error level
1294
(ii) Error message
1294
10.2.36 Supervision of communication setting (Commslv error)
1295
(i) Error level
1295
(ii) Error message
1295
(iii) Setting error information
1295
10.2.37 Supervision of GOOSE publishing (LAN(GOOSE)error)
1297
(i) Error level
1297
(ii) Error message
1297
10.2.38 Aux. contacts monitoring (DPSY/DOPS/TOPS faulty or undefined)
1298
(i) Correspondence between CHK functions and applications
1298
(ii) Error level
1299
(iii) Error message
1299
10.2.39 Setting
1300
10.2.40 Signal (Data ID)
1306
10.3 Trip circuit supervision task
1313
10.3.1 Detecting erroneous operation
1314
(i) Operation logics
1314
(ii) Applications
1314
(ii)-1 Example1
1314
(ii)-2 Example2
1315
10.3.2 Trip circuit error (TC error)
1317
(i) Error level
1317
(ii) Error message
1317
10.3.3 Setting
1318
10.3.4 Signal (Data ID)
1319
10.4 Supervision task of interruption capability on CB
1321
10.4.1 Operation of sigma Iy
1322
10.4.2 Sigma Iy error (CHK_SGMIY error)
1323
(i) Error level
1323
(ii) Error message
1323
10.4.3 Setting
1324
10.4.4 Signal (Data ID)
1325
10.5 Supervision tasks for device dependent features
1326
10.5.1 Error detection of differential current in DIF (Id)
1327
(i) Error level
1327
(ii) Error message
1327
10.5.2 Current transformer failure detected with DIF (DIF-CT)
1328
(i) Error level
1328
(ii) Error message
1328
10.5.3 Synchronizing and sampling error (Com sync fail)
1329
(i) Error level
1329
(ii) Error message
1329
10.5.4 Communication failure (Com fail)
1330
(i) Error level
1330
(ii) Error message
1330
10.5.5 Error signal level for sending (TX level)
1331
(i) Error level
1331
(ii) Error message
1331
10.5.6 Error signal level for receiving (RX level)
1332
(i) Error level
1332
(ii) Error message
1332
10.5.7 Propagation delay error (Com Td)
1333
(i) Error level
1333
(ii) Error message
1333
10.5.8 Error terminal configuration (Term ID)
1334
(i) Error level
1334
(ii) Error message
1334
10.5.9 Monitoring ready state at the remote (Term rdy)
1335
(i) Error level
1335
(ii) Error message
1335
10.5.10 Transmission error (Com fail-R)
1336
(i) Error level
1336
(ii) Error message
1336
10.5.11 Master-slave monitoring (MSCHK)
1337
(i) Error level
1337
(ii) Error message
1337
10.5.12 Supervision of Relay ID (RYID)
1338
(i) Error level
1338
(ii) Error message
1338
10.5.13 Setting
1339
10.5.14 Signal (Data ID)
1342
11 Communication protocol
1345
11.1 Selection of slave protocol
1346
11.2 LAN operation
1347
11.2.1 LAN address (IP address)
1347
11.2.2 Redundant LAN (Hot-standby)
1348
(i) Overview
1348
(ii) Primary port selection
1349
(iii) Llink-down timer
1349
(iv) Link-up timer
1349
(v) PLC switching
1350
(vi) Monitor
1350
(vi)-1 LCD screen: The user can examine the statuses about the communion modules by the monitoring function. Figure 11.2-2 shows the port status about the modules; terms ‘Up’ and ‘Down’ mean running and stopping, respectively. For menus operations, se...
1350
(vi)-2 Status signals for Port A and Port B: The user can also examine the LAN status using PLC signal monitoring points ‘Port1_Link (3100061001)’ and ‘Port2_Link (3100061001)’ of the HOTST function. For example, when the user wishes to monitor the st...
1351
(vi)-3 Monitor setting: The Hot-standby (HOTST) function can send PING packets to remote devices thus enabling the Hot-standby function to monitor the state of the network. The Hot-standby function checks for a response signal from the remote device. ...
1351
(vi)-4 Example1: There is a remote device on the network with the address Ping_IP1. The Hot-standby function sends ping packets to the remote device every five seconds; then the Hot-standby function waits for one second until the Hot-standby function ...
1352
(vi)-5 Example2: It is assumed that there are three remote devices on the network: Ping_IP1, Ping_IP2, and Ping_IP3. The Hot-standby function sends a Ping packet to every remote device every 10 second (i.e., the IED sends a ping packet to a remote dev...
1353
(vii) IP setting example [RedundantMode]=Hot_standby
1355
(viii) IP setting example [RedundantMode]=Fixed
1355
11.2.3 Redundant LAN (PRP/HSR operation)
1356
(i) Overview
1356
(ii) LRE switches
1357
(iii) Entry Forget Time
1357
(iv) Supervision
1358
(v) Monitor
1358
(vi) IP setting example [RedundantMode]=PRP or HSR
1359
11.2.4 Redundant LAN (RSTP operation)
1360
(i) Overview
1360
(ii) Parameters
1360
11.2.5 Settings
1362
11.2.6 Signals (DataID)
1364
11.3 IEC 61850 communication
1366
11.3.1 About protocol
1368
(i) Legacy IEC61850 (i.e., 61850 Editon1)
1370
(ii) 61850 Edition1 with option
1370
(iii) 61850 Edition2
1370
11.3.2 Communication service
1371
(i) Report for SAS
1371
(ii) GOOSE for peer-to-peer communication
1371
(iii) System
1372
(iv) Control mode using GOOSE
1372
(v) Time synchronization using IEC 61850 protocol / SNTP
1372
(vi) File transfer (COMTRADE)
1372
(vii) Manufacturing Message Specification (MMS)
1373
(viii) Generic Substation Events (GSE)
1373
11.3.3 How to manage engineering work
1374
(i) Creating and opening project
1376
(i)-1 Creation of project file
1376
(i)-2 Selection of IED
1376
(ii) Choice of 61850 edition number
1377
(iii) IEC 61850 configuration files
1379
(iii)-1 Exporting and Importing CID/ICD file
1379
(iii)-2 Manage third party CID file
1379
(iii)-3 Mapping application data in IEC 61850
1379
(iv) Mapping signals in signal list to Logical Nodes
1382
(iv)-1 Edit Mapping Data
1382
(iv)-2 Export / Import Mapping Data
1382
(iv)-3 Edit Logical Node
1383
(iv)-4 Edit DataSet
1384
(iv)-5 Edit Report Control Block (RCB)
1385
(iv)-6 Edit GOOSE Control Block
1386
(iv)-7 Edit GOOSE Publish
1387
(iv)-8 Edit GOOSE subscribe
1388
(iv)-9 Edit Control function
1388
(v) Writing the configuration file to IED
1390
(vi) Confirmation of the edition number of IEC61850
1392
11.3.4 Settings for 61850 communications
1393
(i) Setting time for re-sending GOOSE packet
1393
(ii) Setting for 61850 authentication
1393
(iii) Blocking 61850 communication
1393
(iv) Setting ‘keep-alive’ time for TCP
1393
(v) Setting ‘CommTerm’
1393
(vi) Setting test mode
1394
(vi)-1 GOOSE sending block (GOSNDBLK)
1394
(vi)-2 GOOSE receive block (GOSUBBLK)
1394
11.3.5 Selection of a slave protocol
1395
11.3.6 How to supervise in 61850 communication
1395
11.3.7 Quality signal of IEC 61850 communication
1396
(i) U16_00
1397
(ii) U16_01 signal
1401
(iii) Qual_validity
1402
11.3.8 Goose monitoring status in 61850 communication
1403
11.3.9 Feature of IEC61850 Edition1 option
1404
11.3.10 Setting
1405
11.3.11 Signal (Data ID)
1406
11.4 IEC 60870-5-103 communication
1422
11.4.1 Overview
1423
(i) Management
1423
(i)-1 Data management
1423
(i)-2 Process management
1423
(i)-3 Manage IEC 60870-5-103 display
1423
(ii) Configuration†
1423
11.4.2 Requirements in the Master station
1425
11.4.3 Interoperability
1426
(i) Physical layer
1426
(i)-1 Electrical interface in the RS-485
1426
(i)-2 Optic interface
1426
(ii) Application Layer
1426
11.4.4 Communication interface in the IEC 60870-5-103 standard
1427
(i) Spontaneous events
1427
(ii) General interrogation1
1427
(iii) Cyclic measurements
1427
(iv) Commands2
1427
(v) Test mode3
1427
(vi) Blocking of monitor direction4
1427
11.4.5 Editing data of the configuration
1428
(i) Common setting
1428
(i)-1 Setting file remark
1428
(i)-2 Remote operation valid time
1428
(i)-3 Local operation valid time
1428
(i)-4 Measurand period
1428
(i)-5 Function type of system functions
1429
(i)-6 Signal No. of test mode
1429
(i)-7 Signal No. for relative time and fault number
1429
(ii) Setting of time-tagged messages
1430
(ii)-1 Description
1431
(ii)-2 Signal name / signal description
1431
(ii)-3 Type ID
1432
(ii)-4 INF
1432
(ii)-5 FUN
1432
(ii)-6 DPI/Off, DPI/On
1433
(ii)-7 COT
1433
(iii) Setting for time-tagged measurands
1435
(iii)-1 Description
1436
(iii)-2 Signal name / signal description
1436
(iii)-3 Inverse
1436
(iii)-4 Type ID
1436
(iii)-5 INF
1436
(iii)-6 FUN
1437
(iii)-7 COT
1437
(iii)-8 SCL Measurement Name/Measurement Description
1437
(iii)-9 Coefficient
1437
(iv) Setting for General commands
1438
(iv)-1 Description
1440
(iv)-2 Type ID
1440
(iv)-3 INF
1440
(iv)-4 FUN
1441
(iv)-5 DCO/Sig Off Name, Signal Off Desc., DCO Signal On Name, Signal On Desc., Inverse
1441
(iv)-6 Valid time
1441
(iv)-7 ACK/NACK / Ext
1442
(iv)-8 Signal ACK Name/Signal ACK Desc./Signal NACK Name/Signal NACK Desc./Inverse
1442
(v) Setting of Measurands
1444
(v)-1 Description
1445
(v)-2 Type ID
1445
(v)-3 INF
1445
(v)-4 FUN
1445
(v)-5 Name
1446
(v)-6 Measurement Name/Measurement Description
1446
(v)-7 Lower Limit/Upper Limit
1446
(v)-8 Coefficient
1446
11.4.6 Protocol selection
1447
11.4.7 Tips for settings
1448
11.4.8 Setting
1449
11.5 USB communication
1451
11.6 RS485 communication
1452
12 User interface
1453
12.1 Outline
1454
(i) Front Panel
1454
(ii) LCD screen
1454
(iii) LEDs
1454
(iv) Function keys
1455
(v) Operation keys
1455
12.2 HMI operation
1457
(i) Screen and LEDs during normal HMI operation
1457
(ii) Main-menu and Sub-menu
1457
12.3 Record sub-menu
1460
(i) Fault Record
1460
(i)-1 Display fault record
1461
(i)-2 Clear fault record
1462
(i)-3 Clear all information in Fault Record
1462
(ii) Event Record
1463
(ii)-1 Display of Event Record
1463
(ii)-2 Clear of Event Records
1464
(iii) Disturbance Record
1465
(iii)-1 Display of disturbance Record
1465
(iii)-2 Clear of Disturbance Records
1466
12.4 Monitoring sub-menu
1467
(i) Metering
1467
(ii) Binary I/O
1467
(iii) Communication
1468
(iii)-1 LAN sub-menu: the communication port name and status are shown in a line. When the IED has single communication module, or when the IED has communication modules but a communication module is allowed to operate in the IED, an operation status ...
1468
(iii)-2 IEC61850 sub-menu: IP addresses of the devices connecting in IEC61850 are shown in a straight line. Configurations of those IP addresses are available with GR-TIEMS.
1469
(iv) Relay Elements
1470
(v) Statistics
1471
(v)-1 Power Value sub-menu: With regard to statistics item, the name and its value are shown below. The user can also change the unit of each value by the setting1. It is allowed to reset or revise the statistics value2.
1471
(v)-2 Counter sub-menu: the name and number of statistical items are shown in two lines. When an item is revised, a [+] mark is shown at the end of the first line.
1472
(v)-3 Accumulated Time sub-menu: Total time for which the IED has been running is shown in “d (date) h (hour) m (minute)” format. The user can clear the total time value by clear operation (reset), which is shown in Figure 12.4-14.
1473
(vi) GOOSE monitoring
1473
(vii) Diagnostics
1474
12.5 Setting sub-menu
1475
(i) Setting method
1475
(i)-1 Element Setting Mode: The “Element Setting Mode” is used for setting numerical values. For each setting, the setting name, setting value and the unit are displayed in two lines. Figure 12.5-1 provides an example of the element setting mode.
1475
(i)-2 Switch Setting Mode: The “Switch Setting Mode” is a setting used for the selection of two modes. Figure 12.5-3 provides an example of the switch setting mode. For each setting, the setting name and the selected item are displayed on two lines.
1476
(i)-3 List Selection Mode: The “List Selection Mode” is composed of main-setting-screens and selection-list-screens as shown in Figure 12.5-5. In the main-setting-screen, the setting name and the selected item are displayed. Press the key ENTER to beg...
1477
(i)-4 Signal Selection Mode: Figure 12.5-6 shows the steps to select a signal.
1478
(ii) Confirmation dialog in each sub-menu
1479
(iii) On/Off function
1482
(iv) Protection group setting
1482
(iv)-1 Change active group: An example for changing the active group is shown in the following figure.
1483
(iv)-2 Copy group setting: The user can copy an active setting from one group to another group. As an example, in the following figure “Group3” will be copied to “Group2”, as shown in Figure 12.5-12.
1483
(iv)-3 Change group settings: Upon shipment from the factory, the default settings are set. Therefore, in each group, the user can change the settings of the protection functions and other features. To change the settings in each group, refer to the s...
1484
(v) Configuration of Function keys
1484
(v)-1 Screen jump function: To configure the screen jump function, follow the steps as shown in the figure below.
1485
(v)-2 Signal control function: To assign a test signal to a function key, follow the steps as shown in Figure 12.5-16.
1487
12.6 I/O setting sub-menu
1488
(i) AC analog input
1488
(i)-1 Selection of ratio: For example, Figure 5.2-1 shows how the channel selection is made for the AC analog input on a VCT module (AI#1 = VCT#1). Move the cursor by pressing keys ▲ and ▼. Then, press key ►to go to the next level in the hierarchy.
1488
(i)-2 Rating check: Figure 12.6-2 is a check example for channel#1. Using this screen, the user should confirmed DEP being set in each CT channel.
1489
(i)-3 Selection of CT polarity: For example, Figure 12.6-3 shows how change the CT polarity on a VCT module (AI#1 = VCT#1). Using the cursor by pressing keys ▲ and ▼ and pressing key ►, go for required setting items.
1489
(i)-4 Selection of residual voltage: A residual voltage is obtained by the computation in three-phase voltages, but it can be obtain directly from a residual voltage transformer if the transformer is provided exclusively. Figure 12.6-4 shows how to se...
1489
(ii) Binary input
1490
(ii)-1 Selection of binary input circuit: For example, Figure 12.6-5 illustrates the selection of a binary input circuit on a binary IO module. Move the cursor by pressing keys ▲ and ▼. Then, press key ►to go to the next hierarchy.
1490
(ii)-2 CPL setting: Figure 12.6-6 is an example of a “Common” setting. From this screen, the user can set a threshold level and the number of comparisons feature for contact chatter for all binary input circuits.
1491
(iii) Binary output
1492
(iii)-1 Selection of binary output circuit: For example, Figure 12.6-8 illustrates the selection of a binary output circuit on a binary IO module. Move the cursor by pressing keys ▲ and ▼. Press key ► to go to the next level in the hierarchy.
1492
(iii)-2 CPL Setting: For example, Figure 12.6-9 illustrates the setting of a binary output circuit (BO1). Using setting [BI1_CPL] On, the CPL logic in BO1 is available. Similarly, assigned signals, timers and switches can be set in this menu. Note tha...
1492
(iv) Selection and setting of LED
1494
(iv)-1 Selection of LED: Figure 12.6-11 shows the LED selection screen; the user can select a setting item by pressing keys ▲ and ▼. Press key ► to go to the next level in the hierarchy.
1494
(iv)-2 LED Setting: As shown in Figure 12.6-12, the user can set the logical gate, timer, color of LED and assign signals in this screen.
1495
12.7 Time sub-menu
1496
(i) Clock
1496
(i)-1 Time menu
1496
(i)-2 ActiveSyncSrc menu
1497
(ii) Time zone
1497
(iii) Time synchronization
1498
(iii)-1 TimeSyncSrc menu
1498
(iii)-2 SNTP menu
1499
(iii)-3 BI SYNC menu
1499
(iii)-4 IRIG SYNC menu
1500
(iv) Display format
1500
(iv)-1 Date format menu
1500
(iv)-2 Date delimiter menu
1501
(iv)-3 Time delimiter menu
1501
(iv)-4 Second delimiter menu
1502
(v) DST (Summer time)
1502
12.8 Test sub-menu
1504
(i) Test screen
1504
(ii) Test mode screen
1504
(ii)-1 Test option screen: The Test Option screen, shown in Figure 12.8-3, is used to select the following functions and perform a Test flag forced reset.
1504
(ii)-2 Function test screen: Function test screen is provided for testing; the use can program test operations, which can be implemented in protection and control functions. Figure 12.8-4 exemplifies the Test screen. Automatic supervision will stop wh...
1505
(ii)-3 Binary input test screen: The user can have a virtual signal to a binary input circuit using the binary input test screen. Figure 12.8-5 shows an example; the user can select IO#1 or IO#3. (Actually, the content displayed will differ depending ...
1505
(ii)-4 Binary output test screen: The user is able to test a binary output circuit. Figure 12.8-10 is an example of how to select a binary output from the Test Mode screen.
1507
(iii) TestFlag-EN screen
1508
(iv) Mode change screen
1509
(v) Signal monitoring screen
1509
12.9 Information sub-menu
1510
12.10 Security setting sub-menu
1511
12.11 Control sub-menu
1513
(i) CB operation
1514
13 Installation and setting
1515
13.1 Caution for storage
1516
13.2 Handling precautions
1516
13.3 Unpack and inspection of hardware and software
1517
(i) Opening and inspecting relay (IED) package
1517
(ii) Manufacture settings (In, Vn, fn, Vdc)
1517
(iii) Combination of VCT and BIOs
1518
(iv) Communication modules (LAN and others)
1519
(v) Relay and control software
1520
(vi) Flange covers and labels
1520
(vii) White-plastic-sheets for IED case sides
1521
13.4 Changing rated current
1522
Step1: Turn off the IED.
1522
Note that all outputs are locked-out when powered-off†.
1522
Then, open the IED panel. Remove a flat cable and lateral beams in the IED case‡.
1522
Step2: Change CPU mode (Default ( Constrained mode)
1522
To change a CPU mode†, the user shall close a CPU-W6 circuit with a jumper. The user can get jumpers from an optional-kit (EP-221). Insert the jumper on either W6(1-2) or W6(3-4) for changing.
1522
Step3: Change rated current (1A ( 5A)
1523
Pull out VCT module from the IED case.
1523
To shift the rated current to 1A, remove jumpers shown in Table 13.4-2.
1523
To shift the rated current to 5A, insert jumpers shown in Table 13.4-2.
1523
Step4: Take back to the original.
1523
Connect inner flat cable and the power cable†
1523
Step5: Check altered ordering code, which is set on Step 2†.
1523
The user needs to confirm the rated current changed by checking the altered ordering code (at Position K)‡. Figure 13.4-1 illustrates how to confirm the altered ordering code from the nameplate and LCD screen.
1523
Step6: Write settings with altered code
1524
To write the settings corresponding to the altered code, use the GR-TIEMS. For example, after rated current changed to 1A, rewrite the setting items into the IED using the altered ordering code (see Figure 13.4-1 about the altered code; in this examp...
1524
Step7 Confirmation of DEP setting after rewriting
1525
For example for VCT12B, after the initialization (rewriting), the user shall check that DEP is set for Ch6, 7, 8, 9, 14 entirely (see Figure 13.4-3).
1525
Step8: Memo for change rated current
1526
There is Factory setting label on the IED. Marking the altered rated current on it is a good example.
1526
13.5 PWS alarm threshold setting
1527
14 Commissioning and maintenance
1528
14.1 Scope of required test
1529
14.2 Cautions
1530
(i) Safety Precautions
1530
(ii) Cautions on Tests
1530
14.3 Preparations
1530
14.4 Test operations
1532
14.4.1 Test for communication
1532
(i) GOOSE sending block (GOSNDBLK)
1532
(ii) GOOSE receiving block (GOSUBBLK)
1533
(iii) Test flag cancel (S-TestFlagCancel)
1533
(iv) Test for all communication (TestFlag-EN)
1533
14.4.2 Test for relay application
1533
(i) Auto monitoring function (A.M.F)
1533
(ii) Test of cold load protection (CLP-Test)
1533
(iii) Local test (Local-test)
1533
(iv) Local loop test (Loop-test)
1533
(v) Open test (OPEN 1/OPEN 2)
1533
(vi) Stub protection test (DIFL-STUB-Test)
1533
(vii) ZS, ZG test (ZS-Test.CTRL, ZS-Offset.CTRL, ZS/ZG-Test.XAngle)
1534
(vii)-1 ZS-Test.CTRL
1534
(vii)-2 ZS-Offset.CTRL
1534
(vii)-3 ZS-Test.XAngle, ZG-Test.XAngle
1534
(viii) Thermal overload function test (THM-Test, THM-IP)
1534
(ix) SOTF test (SOTF-Test)
1534
(x) STUB test (STUB-Test)
1534
(xi) Under voltage test (UV,UVS-Test)
1534
(xii) ARC shot number test (SHOTNUM-Test)
1534
14.4.3 Test for control application
1535
(i) Synchronizing check test (SYNC01,02-Test)
1535
14.4.4 Test for BI and BO circuits
1535
(i) Binary input circuit test (SLOT*BIxx-SET)
1535
(ii) Binary output circuit test (SLOT*BOxx-SET)
1535
14.4.5 Test for mode change (MDCTRL)
1535
14.4.6 Signal monitor
1535
14.4.7 LED light test
1535
14.5 Setting
1536
14.6 Signal
1537
Appendix 1 Signal list for common function
1538
Appendix 2 Case outline
1545
Appendix 3 Typical external connection
1554
Appendix 4 IEC61850 MICS, PICS, PIXIT, and TICS
1563
(MICS Edition 1)
1564
(PICS Editon1 and 2)
1599
Introduction
1600
ASCI basic conformance statement
1601
ACSI models conformance statement
1602
ACSI service conformance statement
1603
(PIXIT Edition1&2)
1606
1. Introduction
1607
2. CONTENTS OF THIS DOCUMENT
1607
3. PIXIT FOR DOCUMENTATION
1607
4. PIXIT FOR ASSOCIATION MODEL
1608
5. PIXIT FOR SERVER MODEL
1609
6. PIXIT for Data set model
1610
7. PIXIT FOR SUBSTITUTION MODEL
1610
8. PIXIT FOR SETTING GROUP CONTROL MODEL
1610
9. PIXIT for Reporting model
1611
9. PIXIT for Reporting model (continued)
1612
10. PIXIT FOR LOGGING MODEL
1612
11. PIXIT FOR GOOSE PUBLISH MODEL
1613
12. PIXIT FOR GOOSE SUBSCRIBE MODEL
1614
12. PIXIT FOR GOOSE SUBSCRIBE MODEL (continued)
1615
12. PIXIT FOR GOOSE SUBSCRIBE MODEL (continued)
1616
13. PIXIT for GOOSE performance
1616
14. PIXIT FOR CONTROL MODEL
1617
14. PIXIT FOR CONTROL MODEL(Continued)
1618
14. PIXIT FOR CONTROL MODEL(Continued)
1619
14. PIXIT FOR CONTROL MODEL(Continued)
1620
15. PIXIT FOR TIME AND TIME SYNCHONISATION MODEL
1621
16. PIXIT FOR FILE TRANSFER MODEL
1622
17. PIXIT FOR SERVICE TRACKING MODEL
1622
(TICS Edition2)
1623
1. Introduction
1624
2. Mandatory Edition2 Tissues
1625
2. Mandatory Edition2 Tissues (continued)
1626
2. Mandatory Edition2 Tissues (continued)
1627
2. Mandatory Edition2 Tissues (continued)
1628
(Default mapping: Ed.1)
1629
(Default mapping: Ed.2)
1652
Appendix 5 IEC60870-5-103 interoperability
1657
Appendix 6 Ordering
1671
Appendix 7 Technical data
1691
Trip time characteristics (IEC60255-121)
1709
SIR trip time characteristics for three-phase fault (ZS element) [Short line]
1710
SIR trip time characteristics for ground fault (ZG element) [Short line]
1711
SIR trip time characteristics for three-phase fault (ZS element) [Long line]
1712
SIR trip time characteristics for ground fault (ZG element) [Long line]
1713
Appendix 8 Manufacture setting
1714
Appendix 9 Matrix between VCT terminals and relay applications
1716
Appendix 10 CT requirement
1721
Appendix 11 Notes for the dielectric voltage test
1731
Appendix 12 Engineering exercise
1736
(i) CB operation on MIMIC
1737
(i)-1 Preparation: Materials (exercise)
1738
(i)-2 DPOS01 setting (exercise)
1739
DPOS inputs
1739
DPOS outputs
1739
(i)-3 BIO setting (exercise)
1741
(i)-4 ILK setting (exercise)
1742
(i)-5 MIMIC editing (exercise)
1743
(i)-6 Writing setting data (exercise)
1744
(i)-7 Operation (exercise)
1744
(i)-8 Tips (exercise)
1745
(ii) Signal monitor and meter displayed on MIMIC
1746
(ii)-1 Preparation: Materials (exercise)
1746
(ii)-2 Configuration: SPOS symbol editing (exercise)
1747
(ii)-3 Configuration: Metering symbol editing (exercise)
1748
(ii)-4 Writing setting data (exercise)
1749
(ii)-5 Operation (exercise)
1749
(ii)-6 Available signals displayed on MIMIC
1750
5
Based on 1 rating
Ask a question
Give review
Questions and Answers:
Need help?
Do you have a question about the Toshiba GR200 Series and is the answer not in the manual?
Ask a question
Toshiba GR200 Series Specifications
General
Model
GR200 Series
Category
Storage
Type
NAS
RAID Levels
0, 1, 5, 6, 10
Drive Types Supported
3.5" SATA HDD
Host Connectivity
Ethernet
Power Supply
Redundant
Related product manuals
Toshiba 512E
1 page
Toshiba TR200
24 pages
Toshiba CANVIO
960 pages
Toshiba Canvio 1TB
2 pages
Toshiba DT01ACA050
2 pages
Toshiba Canvio Slim
205 pages
Toshiba Canvio 640GB
2 pages
Toshiba FlashAir W-04
64 pages
Toshiba MQ01ABD series
1 page
Toshiba DT01ACA series
1 page
Toshiba microSDXC UHS-?
5 pages
Toshiba FlashAir W-04 Series
5 pages