- 789 -
Table 4.5-4 Mapping signals for ISCSO1 object.
Ctrl/GGIO1301$ISCSO1$origin
Ctrl/GGIO1301$ISCSO1$origin
Note: “Status (ST)” and “Measurement (MX)” are defined in the function constraint (FC)
of the IEC 61850 standard.
Figure 4.5-6 orCat attribute mapped into ISCSO1 object of GGIO1301
(iii) Mapping input data
The TTIM01 function can receive three commands “select, operate, and cancel. Thus, the user
will need to map the input-point “TOTAL01_CMM_REQ”. Table 4.5-5 shows the input-point
“TOTAL01_CMM_REQ” and the Object reference “Ctrl/GGIO1301$ISCSO1$”; the user should
map the input-point to the Object reference having attributes CO and CF in FC†. Figure 4.5-7
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; “CO” stands for “Control”
and “CF” stands for “Configuration” in the functional constraint (FC).