6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 445 -
(ii) Setting logic for ARC2 mode – setting (ARC2-MODE)
The ARC2-MODE input setting is illustrated in Figure 2.34-12. The scheme switch [ARC2-
MODE] is provided similar to the [ARC1-MODE].
&
&
&
&
&
&
&
1
1
&
&
&
&
&
&
&
1
1
1
1
1
1
ARC2-MODE
OFF
FT
SPAR
TPAR
SPAR&TPAR
MPAR
ORIGINAL
From PROT-COMMON
Signal ‘1’ is generated when there is no contradiction between
the various signals, that is only one signal is picking up.
&
&
&
&
&
&
&
1
CB-SYSTEM=2CB
CB-SYSTEM=1CB
ARC2_MODE-OFF
800002EBB0
ARC2_MODE-FT
810002EBB1
ARC2_MODE-SPAR
820002EBB2
ARC2_MODE-TPAR
830002EBB3
800002EBB7
ARC2_MODE-S&T
800001EBB7
ARC2-MODE-MPAR
850002EBB5
800001EBB7
ARC2_MODE-ORG
860002EBB6
1
1
1
ARC2-MODE=OFF
ARC2-MODE=SPAR
ARC2-MODE=TPAR
ARC2-MODE=S&T
ARC2-MODE=ORG
ARC2-MODE=NO-OFF
ARC2-MODE=ON
Initiation
Start
ARC2-MODE=SPAR+S&T
ARC2-MODE=MPAR
1
Condition
Original
CB2_BRIDGE
To TRC
CB2 F.BRIDGE
READY
810002EBB9
8800021B62
Figure 2.34-12 ARC2-MODE input logic