6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 1170 -
8.3.8 Setting
DISTURB_REC(Function ID: 200401)
Setting items
Range
Unit
Contents
Default
Note
Record Time
0.1 - 10.0
s
Time for disturbance recording
3.0
Pre-fault Time
0.1 - 10.0
s
Pre-fault time
0.3
Sampling Rate
7.5 / 15
deg
Sampling electrical degree for recording
15
Interpolate Mode
Off / On
Sampling data interpolated in 15 degree
Off
Trip Trig.SW
Off / On
Operation with the TRC trip command
On
DISTURB_REC(Function ID: 200401)
Setting items
Range
Unit
Contents
Default
Note
Binary Signal1
(Preferred DataID)
Logic signal1 for the operation
See Setting table
in this section
Binary Sig.Name1
(Preferred name)
Name of the logic signal1
Binary Signal2
(Preferred DataID)
Logic signal2 for the operation
Binary Sig.Name2
(Preferred name)
Name of the logic signal2
Binary Signal3
(Preferred DataID)
Logic signal3 for the operation
Binary Sig.Name3
(Preferred name)
Name of the logic signal3
……
……
……
……
……
……
Binary Signal256
(Preferred DataID)
Mode setting for the detection
Binary Sig.Name256
(Preferred name)
Name of the trigger signal768
DRT_LP(Function ID: 4B0001)
Setting items
Range
Unit
Contents
Default
Note
1A rating
5A rating
1A
5A
OC-DRT-EN
Off / On
Disturbance Record Trigger OC-DRT enable
Off
OC-DRT
0.10 -
50.00
0.50 -
250.00
A
OC-DRT relay operating value
1.00
5.00
EF-DRT-EN
Off / On
Disturbance Record Trigger EF-DRT enable
Off
EF-DRT
0.10 -
50.00
0.50 -
250.00
A
EF-DRT relay operating value
0.20
1.00
UV-DRT-EN
Off / On
Disturbance Record Trigger UV-DRT enable
Off
UV-DRT
5.0 - 130.0
UV-DRT relay operating value
0.20
UVS-DRT-EN
Off / On
Disturbance Record Trigger UVS-DRT enable
Off
UVS-DRT
5.0 - 130.0
V
UVS-DRT relay operating value
51.0

Table of Contents