6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 952 -
§§Note: The “TPOS01-PIEX-BO” signal is issued when Fixlogic is set for scheme switch
[TPOS01-LGP1EXOT]. If the signal is to be issued from the programmed logic by
the user instead of the logic shown in Figure 4.9-26, connect the “operate
completed” signal generated in the user-programmed logic to connection point#2
“User configurable condition”. That is, set the scheme switch [TPOS01-
LGP1EXOT] to PLC and use “TPOS01IN_TMP_38”.
Output signal to BO
The TPOS01 function, in Figure 4.9-43, can issue a signal Operate P3-controlat output point
TPOS01_P3EX_BO”, when the TPOS01 function determines that the signal PLC-P3-Control
is true.
(x) Operate condition
In a manner similar to which the conditions have been examined for the select command, the
conditions for an operate command should be understood. Figure 4.9-44 illustrates the logic to
examine an operate condition. The operate condition is determined by signal
TPOS01_STATE. If the functionality of the original logic does not meet with user-
requirements, the following alternatives are provided:
1. The user can replace the original logic with alternative logic,
2. The user can add another signal to the original logic.
Replacing the original logic
If the user wishes to replace the operate condition logic completely, it can be achieved using
PLC connect point “User configurable operate condition”.
1. Connect the user-customized logic using TPOS01IN_TMP_34”, listed as PLC#2 in
Table 4.9-19.
2. Set scheme switch [TPOS01-LGEXFFCT] to PLC.
Adding another operate condition signal
If the addition of another operate condition is required, the user can add the signal to operate
condition logic using PLC connection point “Additional condition”.
1. Add a user-preferred signal using TPOS01IN_TMP_33”, listed as PLC#1 in Table
4.9-19.
2. Set scheme switch [TPOS01-LGEXFFCT] to Fixed logic.