EasyManua.ls Logo

Toshiba GR200 Series - (ii) TPAR mode

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 434 -
(ii) TPAR mode
Figure 2.34-3 illustrates the ARC function when settings of are performed in both Table 2.34-5
and Table 2.34-6.
Table 2.34-5 Block parts in TPAR mode
Corresponding logics
Detailed logic
ARC1-Mode input
Figure 2.34-11
Shot number
Figure 2.34-13
Start
Figure 2.34-14
Initiation
Figure 2.34-15
Shot counter
Figure 2.34-16
Condition
Figure 2.34-17
ARC1 TPAR
Figure 2.34-19
ARC1 SHOT2
Figure 2.34-21
Issuing
Figure 2.34-22
Success check
Figure 2.34-23
Reclose sequence
Figure 2.34-24
Table 2.34-6 Setting examples in TPAR mode
Categories
Items
Settings
Corresponding logics
ARC general
ARC1-EN
On
ARC1-Mode
TPAR
Figure 2.34-11
ARC2-EN
Off
ARC2-Mode
Off
Figure 2.34-12
ARC-ORDER
CB1
Figure 2.34-24
Multi Shot-EN
On
ARC-NUM
S2
Figure 2.34-13
ARC1
TREADY
60.0s
Figure 2.34-15
TTPAR1
0.60s
Figure 2.34-19
TTPAR1_SUB
300.00s
Figure 2.34-19
TRR1
2.00s
Figure 2.34-19
TCCW1
0.20s
Figure 2.34-22
ARC1 multi-shot
TD_MS2
20.00s
Figure 2.34-21
TRR_MS2
30.00s
Figure 2.34-21
ARC misc.
ARC-SucChk
On
Figure 2.34-23
TARCSUC
0.30s
Figure 2.34-23
FT-3pFault
Off
Figure 2.34-14
TRESET
0.30s
Figure 2.34-15
TEVLV
0.30s
Figure 2.34-17
SHOTNUM-TEST
Off
Figure 2.34-16
PROT-COMMON
CB-System
1CB
See Protection common function
VCHK
ARC1-VCHK EN
On
See Voltage check for autoreclose
TRC
TP-MODE
Per-Phase
See Trip circuit

Table of Contents