- 313 -
failure.
(ii) Switch of OVS trip command
The OVS function issues a trip command for the trip circuit (TRC†) when Trip is set for scheme
switch [OVS1-UseFor] as the normal trip operation. However, when an alarm signal in place
of the trip command is required, the user can set Alarm for the scheme switch [OVS1-UseFor].
†Note: For more information, see Chapter
Relay application: Trip circuit
.
(iii) Execution of OVS function
Set On for scheme switch [OVS1-EN]. Otherwise, set Off for the scheme switch [OVS1-EN] if
the OVS1 element is not required to operate.
2.22.5 Scheme logic
Figure 2.22-4 shows the OVS function logic. Signal connection points “OVS1_BLOCK” are
provided for the block of the operation of the OVS elements. For testing, the OVS1-PU element
is provided; it generates a pick-up signal when the entering voltage is excesses of the threshold
anytime. For example, in the IDMT characteristic, using both monitoring points “8000011C20”
and “8000011C24” can facilitate to measure the pickup time after the excess.
The logics of OVS2 and OVS2 PU are the same as the
logics of OVS1 and OVS2 PU.
Figure 2.22-4 OVS function logics