- 720 -
Settings for erroneous contact health check (improper setting, example #2)
Figure 4.2-50 shows a setting example an improper setting of the 43SW scheme. The settings
are implemented incorrectly as shown in Table 4.2-32, BO1-RB is not chosen, instead BO1 is
actually chosen, which is incorrect. In this case, the setting [DPSY01-OSLBORD] is
meaningless; hence, the issue of a select command is blocked.
Table 4.2-32 Erroneous setting example for contact health check
Example #2
Contact health check setting for example #2
“DPSY01_OSL_BO_FLG” is connected to “BO1” Close SLOT1
[DPSY01-OSLBORD] =” 200B018002001112”(BO1)
NG
“DPSY01_FSL_BO_FLG” is connected to “BO2” Close SLOT1
[DPSY01-FSLBORD]=” 200B018102011113” (BO2-RB)
OK
“DPSY01_OEX_BO_CSF” is connected to “BO3” Close SLOT1
[DPSY01-OEXBORD]=” 200B018202021113” (BO3-RB)
OK
“DPSY01_FEX_BO_CSF” is connected to “BO4” Close SLOT1
[DPSY01-OEXBORD]=” 200B018302031113” (BO4-RB)
OK
Plus (+)
SW1 is driven with
BO1 at IO#1
BO1
Drivers
BO3
BO4-RB
(200B01_8302031113)
BO4
BO3-RB
(200B01_8202021113)
SW2 is driven with
BO2 at IO#1
SW4 is driven with
BO4 at IO#1
Local/remote-end
SW 3
SW 1
Minus ()
BIO module
43SW
BO2
BO2-RB
(200B01_8102011113)
SW 2
SW 4
SW3 is driven with
BO3 at IO#1
BO1 (not BO1-RB)
mistakenly chosen with
200B01_8002001112
DPSY01_OSL_BO_FLG
(511001 8602011DC6)
Select command
Closing
Operate command
Closing
DPSY01_OEX_BO
(511001 8202011DD3)
Operate command
Open
DPSY01_FEX_BO
(511001 8102011DD0)
Closing
command
Select command
Open
DPSY01_FSL_BO_FLG
(511001 8A02011DC4)
Open
command
Figure 4.2-50 Contact health check setting and 43SW diagram for example #2