Toshiba GR200 Series - (xi) Signal name and number

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 954 -
4.9-6.
*5
Note: The criteria “unmatched conditions” is determined when “Test-bit status” in a
command is not identical to “IED test status”.
*6
Note: The Function “Event suppression” can detect chattering in BI circuits. (See
4.9.6(i)-3)
*7
Note: A supervision of the Binary IO module can detect connection errors for BI
circuits
.
*8
Note: The Common control (CMNCTRL) function can test or check the operation
direction of logic. When the user sets off for scheme switch [SCDEN], operation
of the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
*9
Note: The user should set scheme switch [TPOS01-DEVTYPE] EDS when the earth-
switch(ES) is applied for the TPOS01 function.
*10
Note: The user must program the PLC logic for Control hierarchy condition” The
user must connect the Control hierarchy condition to the select condition logic
using the connection point TPOS01IN_TMP_21 for more information, see chapter
Control and monitoring application: Control hierarchy
” see PLC#3 of Table 4.9-8.
*11
Note: To identify the input points of the other TPOS, see Table 4.9-8 for PLC#1 to
#3. Note that the logic outputs are generated separately for P1, P2 and P3-
control.
(xi) Signal name and number
Note: The user should note the meaning of the following abbreviations as shown in
column M/O of each table:
“O” signifies that the signal is provided for the optional use.
M signifies that the user should map/set/configure the signal; otherwise, the
user may experience an operational failure if the default settings is used.
N/A signifies that the user cannot change the state of the signal.
Table 4.9-15 PLC connection points (Input signal PLC#1 user a configurable condition)
Signal Number
Signal Name
Description
M/O
513001 800401EE56
TPOS01IN_TMP_27
TPOS01 operate condition configured by the user (for PLC#1)
O
513001 800402EE56
TPOS02IN_TMP_27
TPOS02 operate condition configured by the user (for PLC#1)
O
513001 800403EE56
TPOS03IN_TMP_27
TPOS03 operate condition configured by the user (for PLC#1)
O
513001 800418EE56
TPOS24IN_TMP_27
TPOS24 operate condition configured by the user (for PLC#1)
O
Table 4.9-16 PLC connection points (Input signal PLC#2 user configurable condition)
Signal Number
Signal Name
Description
M/O
513001 820401EE5E
TPOS01IN_TMP_38
TPOS01 operate condition configured by the user (for PLC#2)
O