Selection logic in TPOS01
PLC connection point on BO1
Selection logic for select
command P1 in TPOS01
Selection logic for select
command P2 in TPOS01
Signal captured by
setting [Input signal 1]
“BO1”
(200B01_8002001112)
“BO1-RB”
(200B01_8002001113)
BO1 circuit at IO#1 (Function ID: 200B01)
Connected by
“Programming”
PLC connection point on BO2
Signal captured by
setting [Input signal 1]
“BO2”
(200B01_8102011112)
“BO2-RB”
(200B01_8102011113)
BO2 circuit at IO#1 (Function ID: 200B01)
Connected by
“Programming”
“TPOS01_P1SL_BO_FLG”
(513001 8A04011DC4)
“TPOS01_P2SL_BO_FLG”
(513001 8A04011DC6)
PLC connection point on BO3
Signal captured by
setting [Input signal 1]
“BO3”
(200B01_8202021112)
“BO3-RB”
(200B01_8102021113)
BO3 circuit at IO#1 (Function ID: 200B01)
Connected by
“Programming”
“TPOS01_P3SL_BO_FLG”
(513001 8A04011DC8)
Selection logic for select
command P3 in TPOS01
Figure 4.9-57 Example select connected with BO1-BO3
(iii) BO connection for “operate command”
Figure 4.9-58 exemplifies the connections for operate commands P1/P2/P3; the BO4–BO6
circuits issue the operate command.