- 628 -
(vi) Receiving “Select command Off” by PLC function
Figure 4.1-9 outlines the reception of the select command ‘Off’ by the PLC function.
PLC logic programmed
by the user
Select command Off by PLC
function
Select command Off from remote-end
Select command On from remote-end
Select command Off from front panel
Select command On from front panel
Select command On by the PLC
function
Figure 4.1-11 Outline of select command ‘Off’
Input signal from the PLC function
Figure 4.1-12 shows the select logic when a “Select command Off (PLC-OFF-Control)” signal
is generated by the PLC function. There are two input points for the reception of this signal,
like in the signal “Select command On (PLC-On-Control)” where four are available. That is, if
interlock checking is required, use the connection point (PLC#1:e.g.,
DEV01_OP_INTERLOCK). Alternatively, if the interlock-check is not required, use the
connection point (PLC#2; e.g., DEV01_OP_COMMAND). PLC#1 and PLC#2 is shown Table
4.1-3.