EasyManua.ls Logo

Toshiba GR200 Series - (vi) Receiving “Select command Off” by PLC function; (vi)-1 Input signal from the PLC function

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 628 -
(vi) Receiving “Select command Off” by PLC function
Figure 4.1-9 outlines the reception of the select command Off by the PLC function.
PLC logic programmed
by the user
Select command Off by PLC
function
Signal output
Select
decision
Success
Failed
Selection logic
Selection logics
Cancel logic
Wait for a next command
Cancel command
Wait for a command
Operate logic
Operate command
Cancel logic
Operate logic
Select command Off from remote-end
Select command On from remote-end
Select command Off from front panel
Select command On from front panel
Select command On by the PLC
function
Figure 4.1-11 Outline of select command ‘Off’
Input signal from the PLC function
Figure 4.1-12 shows the select logic when a “Select command Off (PLC-OFF-Control)” signal
is generated by the PLC function. There are two input points for the reception of this signal,
like in the signal “Select command On (PLC-On-Control)” where four are available. That is, if
interlock checking is required, use the connection point (PLC#1:e.g.,
DEV01_OP_INTERLOCK). Alternatively, if the interlock-check is not required, use the
connection point (PLC#2; e.g., DEV01_OP_COMMAND). PLC#1 and PLC#2 is shown Table
4.1-3.

Table of Contents

Related product manuals