EasyManua.ls Logo

Toshiba GR200 Series - (iii) Setting for the primary zone (Zone1 and a short tapped line)

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 153 -
source does not exist behind busbar B. Accordingly, as for the fault on the line AB, the user
should have underreach setting in enough to the zone1
(S)
.
CTI
Busbar A
Busbar B
Zone1(S)
TZ1
X
Reach
U
R
W
X
Line BJ
TZ2
S
TZ3
Busbar C
J
Line CJ
Line AJ
O
S
Zone2(S)
Zone3(S)
TZR1
Zone1(X)
Fault
Figure 2.10-58 Line CJ tapped at junction J
(iii) Setting for the primary zone (Zone1 and a short tapped line)
Suppose the busbar C is tapped at the junction J on the line AB, as shown in Figure 2.10-59.
It is required to have the reach setting in both the zone1(S) and the zone1(U) so as to hold a
part of the entire length of the line as shown in the long-dashed-short-dashed -circle line to
avoid unwanted operations for external faults at busbar C. Consequently, clearing faults by a
delayed zone2 are performed mostly, as shown in the broken-circle line that is operated at an
end of the line AB†.
Busbar A
Busbar B
Reach
U
Line AJ
S
Busbar C
J
Line JK
Line FJ
O
Busbar B
Busbar A
Busbar C
U
S
O
broken-circle line
long-dashed-short-dashed-circle line
dotted-circle line
Figure 2.10-59 Short line CJ tapped at junction J
Note: To solve the problem, we recommend using the distance carrier command
protection or the current differential protection for the multi-terminals line shown
in the dotted-circle line.

Table of Contents

Related product manuals