- 1323 -
Selection of slave protocol
LAN modules are provided for the IEC61850 and other protocols†, and an optional serial
module‡ will be provided for the IEC60870-5-103 slave communication.
Figure 11.1-1 illustrates the IED has both IEC61850 and IEC103, and the user can select one
of two using SLAVE PROTOCOL§ setting of Communication sub-menu. IEC61850 and IEC103
have their own settings. For example, an IED has IEC61850 settings, such as [GOINT],
whereas it has IEC103 settings, such as [103ADDR].
Communication
10:48 1/6
LAN >
USBCOM >
RS485 >
SLAVE PROTOCOL >
IEC61850 >
IEC103 SLV >
SLAVE PROTOCOL
10:48 1/1
Slave Protocol +
IEC61850
SLAVE PROTOCOL
10:48 1/4
IEC61850
IEC103
DNP3.0†
Modbus†
Figure 11.1-1 SLAVE PROTOCOL setting
†Note: Selection and operation is dependent on the IED configurations, which the
customer has determined with the ordering code. Accordingly, the selection and
operation can be unavailable if the protocol is not provided (see p.1322). To
examine the IED configuration, check your ordering code referring
Appendix:
Ordering
.
Neither DNP3.0 nor Modbus is supported here (even though DNP3.0 and Modbus
are displayed on the LCD).
‡Note: We have discussed that optional communication interface (see
Technical
description: Signal processing and communication module
).
§Note: When changing Slave Protocol to “IEC61850”, need to GR-200 IED restarts after
changing this setting item. Please change this item with caution.
CNM_SLAVE (Function ID: 300001)
A type of the protocol selected in the IED