6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 464 -
Settings [ARC-MANOLK]=FT/TPAR/SPAR&TPAR in [MPAR-MODE]=M3
Table 2.34-14 shows the operation results when the setting [MPAR-MODE] is M3 (i.e., M3
means that three unfaulted (healthy) phases exist in the parallel lines; the respective
unfaulted (healthy) phases are different). For setting [ARC-MANOLK]=SPAR&TPAR, the ARC
function operates to recluse the CB in the SPAR scheme when a faulted phase is found in the
paralleled lines.
Table 2.34-14 Tripped phases and mode for CB reclosing in [MPAR-MODE]=M3
TRC tripping with [TP-MODE]=PER-PHASE ARC reclosing mode with setting [MPAR-MODE]=M3
No
Faulted phases
Setting [ARC-MANOLK]
Line RQ
Line ST
FT
TPAR
SPAR&TPAR
A
B
C
A
B
C
Line RQ
Line ST
Line RQ
Line ST
Line RQ
Line ST
1
x
1ΦT→FT
1ΦTTPAR
1ΦT→SPAR
2
x
x
2ΦT→FT
2ΦTTPAR
2ΦTTPAR
3
x
x
x
3ΦT→FT
3ΦT→TPAR
3ΦT→TPAR
4
x
1ΦT→MPAR
(N/A)
1ΦT→MPAR
(N/A)
1ΦT→MPAR
(N/A)
5
x
x
1ΦT→FT
1ΦT→FT
1ΦTTPAR
1ΦTTPAR
1ΦT→SPAR
1ΦT→SPAR
6
x
x
2ΦTMPAR
(N/A)
2ΦTMPAR
(N/A)
2ΦTMPAR
(N/A)
7
x
x
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
1ΦTMPAR
8
x
x
x
2ΦT→FT
1ΦT→FT
2ΦTTPAR
1ΦTTPAR
2ΦTTPAR
1ΦT→SPAR
9
x
x
x
x
2ΦT→FT
2ΦT→FT
2ΦTTPAR
2ΦTTPAR
2ΦTTPAR
2ΦTTPAR
10
x
x
x
3ΦTMPAR
(N/A)
3ΦTMPAR
(N/A)
3ΦTMPAR
(N/A)
11
x
x
x
2ΦTMPAR
1ΦT→MPAR
2ΦTMPAR
1ΦT→MPAR
2ΦTMPAR
1ΦT→MPAR
12
x
x
x
x
2ΦT→FT
2ΦT→FT
2ΦTTPAR
2ΦTTPAR
2ΦTTPAR
2ΦTTPAR
13
x
x
x
x
3ΦT→FT
1ΦT→FT
3ΦTTPAR
1ΦTTPAR
3ΦTTPAR
1ΦT→SPAR
14
x
x
x
x
x
3ΦT→FT
2ΦT→FT
3ΦTTPAR
2ΦTTPAR
3ΦTTPAR
2ΦTTPAR
15
x
x
x
x
x
x
3ΦT→FT
3ΦT→FT
3ΦTTPAR
3ΦTTPAR
3ΦTTPAR
3ΦTTPAR
x: Occurrence of the fault
: Not energized (out of service)
MPAR: To issue a reclose command by ARC_MPAR_COND
TPAR: The TPAR scheme issuing three-phases tripping by ARC_TPAR_COND; then, to
issue a reclose command
SPAR: To issue a reclose command by ARC_SPAR_COND
FT: To abandon reclosing CB after ARC issuing three-phases tripping by FT setting
1ΦT: To issue a single-phase tripping
2ΦT: To issue two-phases tripping
3ΦT: To issue three-phases tripping
(N.A): Tripping and reclosing do not perform