- 606 -
3.7.6 Setting
Counter (Function ID: 540001)
Setting items
Range
Unit
Contents
Default
Note
GCNT01-EN
Off / On
-
Switch for counter01
On
GCNT02-EN
Off / On
-
Switch for counter02
On
GCNT03-EN
Off / On
-
Switch for counter03
On
.
.
.
..
GCNT31-EN
Off / On
-
Switch for counter31
Off
GCNT32-EN
Off / On
-
Switch for counter32
Off
Counter
01
GCNT01-CNTS
NA / On / Off /
OnOff
-
Condition to count at GCNT01
NA
GCNT01-SDB
0 - 999
-
Value about Sending Dead Band at Counter01
0
GCNT01-CNTRV
0 / 1
-
Set number when the counter is rolled up
0
GCNT01-CNTMAX
9 - 2147483647
-
Largest number for counting
999999
GCNT01-DEVNAME
[Preferred name]
-
Name of Counter01
ARC CLOSE
COMMAND
!
GCNT01-HMI
Off / On
-
Display switch of Counter01
Off
Counter
02
GCNT02-CNTS
NA / On / Off /
OnOff
-
Condition to count at GCNT02
NA
GCNT02-SDB
0 - 999
-
Value about Sending Dead Band at Counter02
0
GCNT02-CNTRV
0 / 1
-
Set number when the counter is rolled up
0
GCNT02-CNTMAX
9 - 2147483647
-
Largest number for counting
999999
GCNT02-DEVNAME
[Preferred name]
-
Name of Counter02
Count2 (Not
Assigned)
!
GCNT02-HMI
Off / On
-
Display switch of Counter02
Off
Counter
03
GCNT03-CNTS
NA / On / Off /
OnOff
-
Condition to count at GCNT03
NA
GCNT03-SDB
0 - 999
-
Value about Sending Dead Band at Counter03
0
GCNT03-CNTRV
0 / 1
-
Set number when the counter is rolled up
0
GCNT03-CNTMAX
9 - 2147483647
-
Largest number for counting
999999
GCNT03-DEVNAME
[Preferred name]
-
Name of Counter03
Count3 (Not
Assigned)
!
GCNT03-HMI
Off / On
-
Display switch of Counter03
Off
.
.
.
.
Counter
31
GCNT31-CNTS
NA / On / Off /
OnOff
-
Condition to count at GCNT31
NA
GCNT31-SDB
0 - 999
-
Value about Sending Dead Band at Counter31
0
GCNT31-CNTRV
0 / 1
-
Set number when the counter is rolled up
0
GCNT31-CNTMAX
9 - 2147483647
-
Largest number for counting
999999
GCNT31-DEVNAME
[Preferred name]
-
Name of Counter31
Count31 (Not
Assigned)
!
GCNT31-HMI
Off / On
-
Display switch of Counter31
Off
Counter
32
GCNT32-CNTS
NA / On / Off /
OnOff
-
Condition to count at GCNT32
NA
GCNT32-SDB
0 - 999
-
Value about Sending Dead Band at Counter32
0
GCNT32-CNTRV
0 / 1
-
Set number when the counter is rolled up
0
GCNT32-CNTMAX
9 - 2147483647
-
Largest number for counting
999999
GCNT32-DEVNAME
[Preferred name]
-
Name of Counter32
Count32 (Not
Assigned)
!
GCNT32-HMI
Off / On
-
Display switch of Counter32
Off
!Note: The user can enter a preferred setting name using GR-TIEMS.
Note: The number of counters in the GCNT depends on IED model. We omit the setting
tables of GCNT04 etc. because the setting items are the same except the device
number.