6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 611 -
3.8.2 Mapping for IEC61850 communication
The user can operate the MDCTRL function over the IEC61850 communication after the
mapping using GR-TIEMS. The user should follow steps,
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data
(i) Editing Logical Node
The user should make a logical node (LN) for the MDCTRL function. Figure 3.8-1exemplifies
LN editing; the LN “LLNO” is chosen for the MDCTRL01 for IEC61850 communication. After
the user defining an object “MOD”, the MDCTRL01 logical node can be saved with the name
“LLNO”. Make a definition of the object “MOD” in MDCTRL01 logical node. Either the SBO
mode or the DIR mode can be chosen in the LN editing.
Figure 3.8-1 Defining “MOD” object in LLNO logic node
Defining SBO mode
Figure 3.8-2 exemplifies the settings in LN “LLNO” when the SBO mode is required for the
MDCTRL01 function. In the SBO control, the user should select the following items for the
“LLNO$MOD” using the GR-TIEMS;