Toshiba GR200 Series - (i)-3 Event suppression

Toshiba GR200 Series
1770 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)
- 889 -
Signal acquisition logic in DPOS01
DPOS01_3PH_STATE
(512001 3103011001)
To select and operate
condition logics
[DPOS01-DEVTYPE]
1-Pole
Open
Faulty
Intermediate
Close
Event
Suppression
detector
BI signal selected by
setting [DPOS01A-NOPSG]
[DPOS01-EN]
On
&
BI signal selected by
setting [DPOS01A-NCLSG]
N/O contact
signal
N/C contact
signal
Single phase signals
&
&
1
&
&
&
&
DPOS01
Signals from the
devices
Output
DPOS01_ F_QLT_SPP
(512001 8103011F5F)
BI circuit and DPOS01
Figure 4.8-41 Acquisition of single-phase signal at DPOS01
Note: In Figure 4.8-41 two signals can be issued DPOS01_3PH_STATE and
DPOS01_F_QLT_SPP, which are the same as the ones of the Figure 4.8-40.
Event suppression
If the status of a device chatters for a short time, the DPOS function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPOS function;
hence, event suppression can be required to reduce additional burden created.
The DPOS function has an event suppression detector. The user should take into account
of the scheme switches [DPOS-NELD], [DPOS-TELD] and [DPOS-TELR]†. Set On for scheme
switch [DPOS01-SPPEN].
1 3 5 7
Signal
from device
On
On
On
On
On
On
On
On
2 4 6 8
On
On
On
[DPOS-TELD]
[DPOS-TELR]
[DPOS-NELD]
Suppressed
signal
A
C
D
E
B
Time.................
Figure 4.8-42 Iterative signals and signals suppressed