-    1089 - 
 
5.6.2  LED Indicators 
The LED indicators #1 and #2 are used to indicate the IED statuses. The others (#3 to #26) are 
provided  to  indicate  statuses,  which  the  user  wishes  to  check;  the  settings  or by  the  PLC 
function can control to indicate the statuses. The user can make a new indicator label using 
the label maker of the GR-TIEMS®. (See 
Chapter Engineering tool
) 
 
The  LED  indicators‡  (#3  to  #26)  are  also  provided  as  user-programmable  indicators. 
Figure 5.6-2 shows the schematic diagrams. Each LED indicator can be lit and controlled using 
a logic-gate-switch setting and others. For simplicity, we discuss setting the LED indicator #3 
only, but the user can take account that setting the other LED indicators (#4 to #26) is the 
same as the #3. Table 5.6-1 shows the LED indicator settings; Table 5.6-2 shows the signal 
monitoring points on all LED indicator logics. 
 
‡Note: Setting menus of the LED indicator are also discussed in Chapter 
User interface: 
I/O setting sub-menu
. 
 
(i)  Selection of input signals 
The LED indicator (#3) is lit by entering signals from other functions; eight ports are provided 
for the entering signals, designated as 
input-signal1
 to 
input-signal8
. The user should ensure 
one  or  more  DataIDs  are  set  for  the 
input-signal1
  to 
input-signal8
.  Entering  signals  are 
designated using DataIDs, respectively; the user should set respective DataIDs for the settings 
[Input signal1] to [Input signal8]. 
 
(ii)  Logic gate switch 
In the LED  indicator  logic  #3  a  logic  scheme  is provide for  the  eight entering signals; the 
entering signals are grouped by the selection using scheme switch [LOGIC-SW] for which the 
user should set either AND, OR or XOR.